Notes On Connecting An Easy Communication Module - Eaton easyE4 Manual

Hide thumbs Also See for easyE4:
Table of Contents

Advertisement

1.10.5 Notes on connecting an easy communication module

EASY-COM-... easy communication modules can be used with an easyE4 base device
starting with generation 05.
(ID on the nameplate, → page 35)
The easy communication module needs to be connected to the left side of the easyE4
base device, while an I/O expansion for easyE4 control relays is connected to the
right side.
It may be necessary to update the firmware on the easyE4 base device
before use.
Only available on firmware version 1.30 or higher.
Each easyE4 base device can only support one easy communication
module.
The easy communication modules are configured in easySoft 8.
Special details regarding SmartWire-DT
easySoft 8 offers planning and ordering help that can be used to configure the
SmartWire-DT line.
This SmartWire-DT planning and ordering help will assist you with selecting and con-
figuring the SmartWire-DT modules on the SmartWire-DT line. The program has the
current consumption specifications for all SmartWire-DT modules. During planning, it
will automatically calculate and display the corresponding system's current con-
sumption.
To set up a SmartWire-DT line and install and run easyE4 as a SmartWire-DT coordin-
ator, you will need to be familiar with the basic contents in the SmartWire-DT doc-
uments.
The inputs and outputs on an SWD line are available alongside the
inputs and outputs for I/O expansion for control relay easyE4. The lim-
itation lies in the number of operands used in the *.e80 project.