Chapter 5: Troubleshooting

The Celltron Advanced requires troubleshooting basic areas of the unit. The sections below
describe what you need to maintain and troubleshoot your Celltron Advanced.
If you have problems with the printer, IR receiver, or temperature sensor, refer to their manuals
or call Midtronics Customer Service at 800.776.1995.

Screen does not light during testing

Possible reasons

If the screen does not light when you test a jar, check the connection to the jar.
• Jar voltage might be too low (<1 V) to test.
• Analyzer battery might need to be replaced.
• A fuse might be blown.

Replacing the analyzer battery

Replace the analyzer battery if the display does not light when you press
To replace the battery in the analyzer:
1. Unscrew the screw on the battery cover with a Phillips screwdriver.
2. Insert a new 9 V battery, aligning the battery terminals.
3. Screw on the battery cover.
If the analyzer fails to advance to the next jar count, try to retest. If the problem persists, call
Midtronics Customer Service at 800.776.1995.

Replacing a fuse

To replace a fuse:
1. Unscrew the fuse holder on the top of the analyzer. Refer to Figure 1 in Chapter 1.
2. Remove the fuse.
3. Insert a spare fuse included with the analyzer or a 5 x 20mm, 1.25 A fuse.