Chapter 2: Pre-Testing; Determining A Reference Value; Reference Values; Options - Midtronics Celltron Advanced CTA-2000 Instruction Manual

Stationary battery string analyzer
Table of Contents

Advertisement

Chapter 2: Pre-testing

Before you test a string with the analyzer, you need to:
• Determine a reference value
• Set options in the
• Set values in the
Make sure the jars you are testing are 2, 4, 6, 8, or 12 V jars.
Note:

Determining a reference value

Reference values

Reference values are average conductance values from a sample of strong jars similar in
condition and age. You can compare reference values to test results from a string. The
differences between test results and reference values help you determine the capacity of the
string to see if it is providing enough conductance for the load. Differences can reflect how a
string was treated, installed, or maintained.

Options

Midtronics recommends that you create your own reference values for a string to get values
specific to the string you are testing. For this reason, the following options are listed in the order
you should take to obtain a reference value.
To obtain a reference value for a string:
1. Consult your company documentation for previous reference values that were created for
the string you are testing. If you do not have previous reference values for the string, do
step 2.
2. Test a sample of jars. Refer to "Testing a sample of jars." If you cannot test a sample of
jars, do step 3.
3. Test the jars in the string that you need to test with the analyzer and use highest
conductance value as a reference value. If you cannot test the jars for a reference value,
do step 4.
4. Use the average from
average in
STRING SUMMARY
5. Contact the jar manufacturer or Midtronics for a list of reference values for common jar
types:
• www.midtronics.com
• 800.776.1995
menu
UTILTIES
menu
SET PARAMETERS
STRING SUMMARY
").
after you test the string. Refer to "Using the
10

Advertisement

Table of Contents
loading

This manual is also suitable for:

Celltron advanced cta-4000

Table of Contents