F005
FM Output Terminal Function
FM
Program  Terminal  Analog Output Terminals
This parameter is used to set the output function of the FM analog output
terminal. The FM output terminal produces an output current or voltage that is
proportional to the magnitude of the function assigned to this terminal (select
current or voltage at F681). The available assignments for this output terminal
are listed in
Note:
To read voltage at this terminal connect a 100 – 500Ω resistor
from the FM (+) terminal to the CC (-) terminal. Using a
voltmeter read the voltage across the 100 – 500Ω resistor.
To read current at this terminal connect a 100 – 500Ω resistor
from the FM (+) terminal through a series Ammeter to the
CC (-) terminal.
The FM analog output has a maximum resolution of 1/1024 and
a maximum load rating of 500 ohms.
FM Terminal Setup Parameters
F005
F006
F681
F682
F683
FM Output Terminal Adjustment
Program  Terminal  Analog Output Terminals
This parameter is used to calibrate the FM analog output.
To calibrate the FM analog output, connect a meter (current or voltage) as
described at F005.
With the ASD running at a known value (e.g., output frequency), adjust this
parameter until the assigned function produces the desired DC level output at
the FM output terminal.
See
F005
ACE-tronics G9 ASD Installation and Operation Manual
efesotomasyon.com -Toshiba inverter,drive,servo,plc
Table 8 on pg.
240.
— FM Output Terminal Function
— FM Output Terminal Adjustment
— FM Voltage/Current Output Switching
— FM Output Gradient Characteristic
— FM Bias Adjustment
for additional information on this setting.
Direct Access Number — F005
Parameter Type — Selection List
Factory Default — Signed Speed
Feedback (Realtime)
Changeable During Run — Yes
Direct Access Number — F006
Parameter Type — Numerical
Factory Default — 493
Changeable During Run — Yes
Minimum — 1
Maximum — 1280
F006
81