F100
Low Speed
Low-Speed Signal Output Frequency
Program  Terminal  Reach
The Low-Speed Signal Output Frequency parameter sets a frequency
threshold that activates the assigned output terminal for the duration that the
ASD output is equal to or above this setting (see
available output assignments).
Reach
Speed Reach Frequency
Frequency
Program  Terminal  Reach
The Speed Reach Frequency sets a frequency threshold that, when reached or
is within the bandwidth specified by parameter F102, activates the assigned
output terminal for the duration that the ASD output is within the bandwidth
specified (see
This setting is also a permissive when using the Express Speed function.
Speed Reach Detection Band
Program  Terminal  Reach
This parameter sets the bandwidth of the Speed Reach Frequency (F101)
setting.
Input Terminal Priority
Program  Terminal  Input Special Functions
This parameter is used to allow the Jog and DC Injection Braking input
signals to control the ASD when received via the ACE G9-120V-PCB even
though the system is in the Local mode.
With this parameter enabled, a Jog command or a DC Injection Braking
command received from the ACE G9-120V-PCB will receive priority over
commands from the EOI.
See
F260
See
F250
Settings:
Disabled
Enabled
90
efesotomasyon.com -Toshiba inverter,drive,servo,plc
Table 10 on pg. 242
for the available output assignments).
for additional information on using the Jog function.
F252
for additional information on DC Injection Braking.
Table 10 on pg. 242
for the
ACE-tronics G9 ASD Installation and Operation Manual
Direct Access Number — F100
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
Direct Access Number — F101
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
Direct Access Number — F102
Parameter Type — Numerical
Factory Default — 2.50
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
Direct Access Number — F106
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — No
F106