F719
ASD Disposition at ST Deactivation
Program  Special  Operation Panel Parameters
Upon deactivation of the ST terminal (if so configured; see F110) while
operating in the Local mode, the ASD output to the motor will cease — this
parameter setting is used to allow for the restart of the motor (ASD output)
without user intervention upon the reactivation of the ST terminal.
Upon reactivation of the ST terminal in this condition the ASD will resume the
Run condition and the motor will start (Retain Panel Run Command).
This feature may be Disabled and the Run command must be re-initiated by the
user for ASD operation (Clear Panel Run Command).
DANGER
WHEN ENABLED THE ASD WILL RESUME THE RUN CONDITION
WHEN THE ST TERMINAL IS REACTIVATED.
Settings:
Clear Panel Run Command
Retain Panel Run Command
Panel Stop Pattern
Program  Special  Operation Panel Parameters
While operating in the Local mode this parameter determines the method used
to stop the motor when the stop command is issued via the EOI.
The Decel Stop setting enables the Dynamic Braking system that is setup at
F304
or the DC Injection Braking system that is setup at F250, F251, and
F252.
The Coast Stop setting allows the motor to stop at the rate allowed by the
inertia of the load.
Settings:
Deceleration Stop
Coast Stop
Note:
The Stop Pattern setting has no effect on the Emergency Off
settings of F603. This parameter may also be accessed by
pressing the ESC key from the Frequency Command screen.
Panel Torque Command
Program  Special  Operation Panel Parameters
This parameter provides a torque value to be used in the event that Panel
Keypad
(F725
Setting) is selected at parameter F420.
ACE-tronics G9 ASD Installation and Operation Manual
Direct Access Number — F719
Parameter Type — Selection List
Factory Default —
Retain Panel Run
Command
Changeable During Run — Yes
Direct Access Number — F721
Parameter Type — Selection List
Factory Default — Deceleration Stop
Changeable During Run — Yes
Direct Access Number — F725
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — -250.00
Maximum — +250.00
F725
193