Installation

• Mount in 2-gang U.S. wallbox 3.5 in (89 mm)
deep or 4 × 4 in (102 × 102 mm) junction box
2.1 in (53 mm) deep. Indoors only.
• This device generates heat; mount only where
ambient temperature is 32 °F to 104 °F (0 °C to
40 °C).
• Mount with arrows facing up to ensure adequate
cooling.
• Allow 4.5 in (114 mm) above and below unit and
between faceplates when mounting several in a
vertical layout.
• Mount so line (mains) voltage wiring is at least
6 ft (1.8 m) from sound or electronic equipment
and wiring.
4
Power Modules
5.1 in
(129.5 mm)
Side Views:
Phase-Adaptive Module
3-Wire Fluorescent/Switching Modules
• Mount within 7° of true vertical.
• Provide 12 AWG (2.5 mm
minimum) for input power and load circuit.
• Strip 1/2 in (12 mm) insulation from wires before
connecting.
• Tighten securely to 4.8 in-lbs (0.55 N•m)
• Run separate neutral for load circuit; no common
neutrals.
Note: Plastic faceplate must be installed on
module for normal operation (all models).
1.2 in (30.5 mm)
1.4 in (35.5 mm)
1.2 in (30.5 mm)
1.0 in (25 mm)
) copper wires (75 °C