9. Specifications

Parameter
AC Load Rating
No of Outlets
Measurement
Voltage
Accuracy
Current
Power
Energy
Timestamp Accuracy
Network Port
Weight
Dimensions
Length:
(Enclosure)
Width:
Depth
Temperature Range:
100% Load
Humidity Range
Altitude
Agency
Safety
Listings
EMC
IP protection class
AC Power System Type
Pollution Rating
© 2023 AMETEK SurgeX | Technical Support 800-645-9721 | surgex.com
SX-VS-128
SX-VS-1216
12A @ 120V
12A @ 120V
8
16
± 2%
± 5%
± 5%
± 5%
± 1%
10/100 Ethernet connection on Female RJ-45, Auto Negotiating with 10/100 network connections with
Link and Activity LEDs
USB RNDIS Device on micro-AB
9.0Lbs/4.1Kg
14.1Lbs/6.4Kg
23.62"/600mm 42.52"/1080mm 59.06"/1500mm 23.62"/600mm 42.52"/1080mm 59.06"/1500mm
2.76"/70.1mm
2.76"/70.1mm
2.6"/66mm
2.6"/66mm
5% to 95% R.H. Non-condensing
0 - 10000ft (0 - 3048meters)
• UL 62368-1, 2nd Ed, 2014-12-01 (Audio/video,
information and communication technology
equipment Part 1: Safety requirements)
• CAN/CSA C22.2 No
• RoHS: Compliant
• Prop 65
• EN 55024:2010
• EN 55032:2015 + AC:2016
• EN 61000-3-2:2014
• EN 61000-3-3:2013
• FCC 47 CFR PART 15 SUBPART B:2020
• ICES-003 ISSUE 6:2016-01 Updated 2019-04
Item Number
SX-VS-1624
SX-VS-108i
16A @ 120V
10A @ 240V
24
8
17.8Lbs/8.1Kg
9.0Lbs/4.1Kg
2.76"/70.1mm
2.76"/70.1mm
2.6"/66mm
2.6"/66mm
0 to 45 °C (32 - 113 °F)
• UL 62368-1-14, 2nd Ed, Issued: 2014-12-01
(Audio/video, information and communication
technology equipment Part 1: Safety requirements)
National Differences specified in the CB Test
Report.
• CE Mark
• UKCA Mark
• WEEE
• RoHS: Compliant
• REACH: Compliant
IPX0
TN
Pollution degree (PD) PD 2
User Manual
SX-VS-1016i
SX-VS-1624i
10A @ 240V
16A @ 240V
16
24
13.9Lbs/6.4Kg
17.6Lbs/8.0Kg
2.76"/70.1mm
2.76"/70.1mm
2.6"/66mm
2.6"/66mm