Specifications - Ametek SurgeX Squid SX-DC-8-12-120 User Manual

Networked power conditioning and energy management ac/dc pdu
Table of Contents

Advertisement

9.

Specifications

Parameter
AC Load Rating
North America
Maximum Full Load
Rest of World
DC Load Rating
Maximum Full Load
SX-DC-8-12-X
SX-DC-8-24-X
SX-DC-8-1224-X
Power Requirement (no load)
DC Efficiency
Audible Noise at 1m
Heat Generation
Normal mode (50Ω load)
Common Mode (50Ω load)
EMI/RFI Filter
Under-Voltage Auto Shutdown
Over-Voltage Auto Shutdown
Over-Current Auto Shutdown
Measurement Accuracy
Timestamp Accuracy
Network Port
Dimensions
Weight
SX-DC-8-12-X, SX-DC-8-24
SX-DC-8-1224
Temperature Range:
Humidity Range
Agency Listings
© 2021 AMETEK Power Quality Solutions | Technical Support 800-645-9721 | surgex.com
Voltage
Current
Power
Energy
-X
-X
SX-DC-8-12-X
SX-DC-8-24-X
SX-DC-8-1224-X
Specification
12 Amps at 120 Volts
10 Amps at 240 Volts
DC Output 1
DC Output 2
Rating
Rating
5A @ 12V
5A @ 12V
2.5A @ 24V
2.5A @ 24V
2.5A @ 24V
5A @ 12V
15 Watts
90% Typical
35 dBA Typical
185 BTU/h Max
> 30 dB 80 kHz – 50 MHz
> 20 dB 160 kHz – 27.5 MHz
> 30 dB 310 kHz – 17.6 MHz
Adjustable from 0V to 300V, or disabled.
Adjustable from 125V to 300V, or disabled.
Adjustable from 0.1A to 20A, or disabled.
± 2% Typical Product Accuracy
± 2% Typical Product Accuracy
± 2% Typical Product Accuracy
± 2% Typical Product Accuracy
± 1% Typical Product Accuracy
10/100 Ethernet connection on Female RJ-45, Auto Negotiating with
10/100 network connections with Link and Activity LEDs
USB RNDIS Device on micro AB
1.75"D x 10"L x 8.25"H
5 lb.
5.5 lb.
100% Load
5C to 39C
5C to 47C
5C to 42C
0% to 95% R.H. Non-condensing
UL/CUL/CB 62368
User Manual
Combined DC1 +
5V Output Rating
DC2 Rating
10A @ 12V
3A @ 5V
5A @ 24V
3A @ 5V
NA
3A @ 5V
31

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents