Ametek SurgeX Vertical+ Series User Manual page 15

Switched ip controllable vertical pdu
Table of Contents

Advertisement

4.4.1.2 Outlet Configuration
Item
Outlet Description
Outlet Name
Reboot Time
Initial State
© 2023 AMETEK SurgeX | Technical Support 800-645-9721 | surgex.com
The Outlet Configuration tab allows for the specification of unique names and reboot times per
outlet. The configuration for initial state per outlet is also here, if this option is selected in the Device
Configuration tab for either On Power Up or On Shutdown Clear.
Description
A fixed short phrase that references a physical feature.
Specifies the name label to be associated with this Outlet
Number of seconds that the device will wait in between turning an outlet off and turning the outlet back
on during a reboot command.
The state that an outlet will assume during start up or after a shutdown clears, if the initial state setting
is selected in the Device Configuration tab. Options are as follows:
Always On
Regardless of other settings, this outlet will always be on. Ignores Shutdown state
and deselecting Initial State in the Device Configuration tab. Outlet ignores user
commands to reboot or power off. The only thing that will kill power with this selected
is a hard reboot, or of power outage.
Always Off
The opposite of Always On, this setting will never allow an outlet to pass power.
On
The outlet will start in an On state.
Off
The outlet will start in an Off state.
Last
The outlet will assume the last state it was in. (Factory Default)
Reboot Only
The outlet will act like the On state but will ignore user commands to power off. This
outlet will only respond to reboot commands. Useful for network appliances that may
need to be rebooted, but otherwise want to be on all the time. Using this setting, the
outlet will still turn off during Shutdown state.
Outlet Configuration
User Manual
15