4.
LINKING TO THE AnACPU (WITH DEDICATED INSTRUCTIONS)
AND THE AJ71 PT3243
MELSEC-A
n2 : Receive buffer cleared/not cleared setting
for each remote ter-
minal number
b15
to
bO
0 0
t
1
t
t
For remote terminal module No. 1
For remote terminal module No. 2
For remote terminal module No.
14
0: Not cleared
1
: Cleared
Setting contents are written to address 858 in the AJ71PT32-S3
buffer.
n3 : Clear execution range setting for each remote terminal number
b15
to
bO
0 0
*
*
For remote terminal module No. 1
For remote terminal module No. 2
For remote terminal module No. 14
0: Only the remote terminal receiveddata areas of the
master module are cleared.
1
: The remote terminal received-data areas of the master
module and the A64RDC receive buffer are cleared.
Setting contents are written
to address 859 in the AJ71PT32-S3
buffer.
(7) When automatic refresh
is being set, MINI-S3 link error detection
X(n+24) of control
1/0
signals assigned to an AJ71 PT32-S3 turns
ON
for
one scan after error detection.
4-32