Mitsubishi MELSEC-A A64RD3C User Manual page 72

Pt100 input module

Advertisement

4.
LINKING TO THE AnACPU (WITH DEDICATED INSTRUCTIONS)
AND THE AJ71 PT32-S3
MELSEC-A
4.4.6
Conversion-completed flag (address 19)
Address 19 is used to confirm that a conversion-enabled channel can detect
temperature correctly.
(1)
The conversion-completed flag processing
after power ON is only per-
formed once when the channel specification for conversion-enabled/dis-
abled (address
0)
is changed.
Conversion-enabled/disabled specification change from
0
to
1
:
After setting conversion-enabled and storing a detected temperature
value in the buffer, the conversion-completed flag
of its corresponding
channel is set to 1.
Conversion-enabled/disabled specification change from 1 to
0:
The conversion-completed flag of its corresponding channel is set to
0.
(2) A conversion-completed flag is provided to each channel.
b15
b14
b13
b12
b l l
b10
b9
b8
b7
b6
b5
b4
b3
b2
b l
b O
0
C H I
CH2
CH3
CH4
0
0
0
0
0
0
0
0
0
0
0
Channel specifications
1
: Conversion completed
0
: Conversion not completed
(3)
The conversion-completed flag can be used
for the interlock when
reading the detected temperature value of the channel where averaging
processing is executed.
4.4.7
Type specification of a platinum temperature-measuring resistor (address 20)
This area is used
to set the type
of a platinum temperature-measuring
resistor.
(1)
When the power supply
is turned ON, the type is set to "0", indicating
the new JIS, DIN type.
(2) All channels correspond to a specified type.
b15
b14
b13
b12
b l l
blO
b9
b8
b7
b6
b5
b4
b3
b2
b l
bO
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
/Q
1
' -
I
These are ignored.
Old JIS/New JIS, DIN-type
designation
J
1
: Old JIS
0 : New JIS. DIN
See Section 2.3.6 for platinum temperature-measuring resistor
4 - 18