6. INSTALLATION AND PRE-OPERATION SElTING PROCEDURES
MELSEC-A
(2) Connecting an AJ71 PT32-S3 and an A64RDC
I
I
I
I
AJ35PTF-24T
AJ71 PT32-S3
A64RDC
(MINI-S3 remote
output
module)
.
i
I
The following table shows the names
of modules and corresponding
terminal screws used
to connect twisted-wire-pair cables.
Also use
appropriate crimp contacts.
Module
Terminal Screw
Tightening Torque Range
kg.cm (Ib-in)
A2CCPU
A64RDC
A2CI/O module
8 . 5
(7.36)
to 1 1 . 5
(9.96)
M3.5
I
MELSECNET/MINI-S3 remote 1/0
module (batch refresh type)
I
M4
1
8
(6.93) to 14 (12.1)
I
PRECAUTIONS
I
Twisted-wire-pair cables must be connected
so that they
may not
be
influenced by noise or surge induction.
(1) Do not lay the cables close to or bind them together with main circuit
wires. (allow 100 mm or more clearance)
(2) When connecting to the remote module terminal block, allow maximum
clearance between twisted-wire-pair cables and module power supply
lines and I/O signal wires.
(3) Do not use a part of twisted-wire-pair cables (such as one pair among
3
pairs) for power supply.
6 - 13