Mitsubishi MELSEC-A A64RD3C User Manual page 41

Pt100 input module

Advertisement

3.
LINKING TO THE A2CCPU
MELSEC-A
3.4.3
Averaging timelcount (addresses 2 to 5)
Addresses 2 to 5 are used to set the length of time or the number of times of
averaging.
(1) When the power is turned ON, the averaging time and averaging count
are set to
0.
(2) The setting ranges are as indicated below:
Averaging in terms of time
: 160 to 32000 msec
Averaging in terms of count
: 1 to 800 times
If a value outside the above range has been written, a setting error occurs
and the buffer is overwritten.
However, the A64RDC performs conversion processing at the averaging
time or count previously set.
IREMARKJ
See Section 2.3.3 for the length of time and the number of times of averaging
3.4.4
Detected temperature value (addresses
6
to 17)
Addresses 6 to 17 are used to store detected temperature values which are
handled in 16-bit or 32-bit data.
(1)
16-bit data (addresses 6 to
9)
A detected temperature value is multiplied by 10 and represented in the
range from -1
800
to 6000 of 16-bit signed binary numbers.
If a detected temperature value is negative, it is represented in a
complement of 2.
Example 1:
If a detected temperature value is 123.025"C (253.445"F), 1230 is
stored.
b15
b14
b13
b12
b l l
b10
b9
b8
b7
b6
b5
b4
b3
b2
b l
b O
0
0
0
0
0
1
0
0
1
1
0
0
1
1
1
0
Example 2:
If a detected temperature value is -123.025"C (-1 89.445"F), -1230 is
stored.
b15
b14
b13
b12
b l l
b10
b9
b8
b7
b6
b5
b4
b3
b2
b l
b O
1
1
1
1
1
0
1
1
0
0
1
1
0
0
1
0
3 -