Download Print this page

Mitsubishi MELSEC-A A64RD3C User Manual page 64

Pt100 input module

Advertisement

4.
LINKING TO THE AnACPU (WITH DEDICATED INSTRUCTIONS)
AND THE AJ71 PT32-S3
MELSEC-A
(1)
Reset switch ON-detected flag X(n+5) and reset switch ON-detected flag
reset Y(n+5) signals.
Turns
ON
(latched) when the A64RDC is reset by using the reset switch.
When both the reset switch ON-detected flag X(n+5) and the reset switch
ON-detected flag reset signal Y(nt5)are turned ON, the FROM/TO in-
struction information
of
the corresponding remote terminal module,
stored in the request-to-communicate registration area, is cleared.
Turn ON the reset switch ON-detected flag reset signal Y(n+5) with the
sequence program.
Reset switch on the front
ON
of the A64RDC
OFF
Reset switch ON-detected
ON
flag X(n+5)
Reset switch ONdetected
ON
flag reset Y(n+5)
OFF
OFF
To
be turned ON and OFF
by the sequence program.
(1)
I f the A64RDC is reset by using the reset switch,
it
returns to the initial
state. Restart the operation with the initial setting.
(2) Since the reset switch ON-detected flag X(n+5) also goes
ON
after the
power is turned ON, be sure to turn the reset switch ON-detected flag
reset signal Y(n+5) ON and the X(n+5) OFF at the initial state. Then,
execute the program for the A64RDC.
4 - 10

Advertisement

loading

This manual is also suitable for:

Melsec-a a64rd4c