Mitsubishi MELSEC-A A64RD3C User Manual page 45

Pt100 input module

Advertisement

3. LINKING TO THE A2CCPU
MELSEC-A
3.5.2
Initial setting of an A2CCPU
The A2CCPU allows connection
of up to
1 4
remote terminals (such as
A64RDC modules). In order to use those remote terminals, it is necessary to
set the remote terminal information in the A2CCPU in the initial setting.
The setting procedure varies with the system disk such as SW4GP-GPPAEE
and the previous type used for booting. Table
3.3
shows the setting proce-
dures including the setting descriptions and the differences between types
of
system disks.
Table 3.3 Initial Setting Descriptions and Procedures
T
Procedures
Setting
Range
Descriptions
Item
SW4GP-GPPAEE
Previous Type
System FD
Total number of
stations
Set the total number of stations including
the remote 1 / 0 modules and remote
terminal modules.
1 to 64
Parameter setting
09036
Set the station number (head station num-
ber) set with the station number setting
switch of each remote terminal module.
D9021
09022
09023
09034
terminal
module
No. 2 remote
terminal
module
No. 3 remote
terminal
module
I
A64RDC
I
Set station
number No. 1
Head station
number
1 to 61
Parameter setting
Set station
number No. 5
I
I
I
I
No. 1 remote terminal module = 1
No. 2 remote terminal module = 5
No.
14
remote
Set the protocol used for data communica-
tions with the remote terminal modules
0
: MINI standard protocol
1
: No protocol
Must be set at
"0".
Protocol
0
to 1
Parameter setting
D9035
Set the processings after the line
error
return and when a line error occurs.
0 : Automatic online return enable
1
: Automatic online return disable
2
: Transmission stop at online error
Mode
0 to
2
Parameter setting
09173
3 -
19