3. LINKING TO THE A2CCPU
MELSEC-A
3.4.2
Averaging processing specifications (address 1)
Address
1
is used to designate execution
of
sampling or averaging.
(1)
When the power is turned ON and the READY signal of the A64RDC is
ON, all channels are set
for
sampling.
(2)
Use buffer address
1
to select sampling
or
averaging.
b15
b14
b13
b12
b l l
b10
b9
b8
b7
b6
b5
b4
b3
b2
b l
b O
-
-
CH1
CH2
CH3
-
-
-
CH1
CH2
CH3
CH4
-
-
-
Ignored
Specifying
the
channel
where
Ignored
Specifying
time/count
averaging
will
be done.
1 : Time averaging
1
: Averaging
0
: Count averaging
0 :
Sampling
When averaging is not specified, sampling is set without regard
to the
time/count specification.
(REMARK[
See Section 2.3.3 for sampling and averaging.