F11.2x:Monitoring Parameter
Parameter
Name
(Address)
F11.20
Keyboard display item
(0x0B14)
settings
F11.21
Speed display factor
(0x0B15)
F11.22
Power display factor
(0x0B16)
F11.23
Monitoring parameter
(0x0B17)
group display selection
F11.24
Monitoring parameter
(0x0B18)
filtering selection
Display selection when
F11.25
the motor is
(0x0B19)
self-learning
F11.27
Fault display selection
(0x0B1B)
4.15 F12:Communication Parameter
F12.0x:MODBUS Slave Parameter
Parameter
Name
(Address)
F12.00
Host-slave choice
(0x0C00)
Modbus
F12.01
communication
(0x0C01)
address
F12.02
Communication baud
(0x0C02)
rate selection
F12.03
Modbus data format
(0x0C03)
AC310 Series Frequency AC Drive Manual
Content
V/F SVC FVC PMVF PMSVC PMFVC
Unit digit: Output frequency display selection
0: Target frequency 1: Operating frequency >=2: Target frequency,
the filtering depth increases with this value
Ten: reserved
Hundreds: Power Display Dimensions
0: Power display percentage (%) 1: Power display kilowatt (KW)
Thousands: reserved
V/F SVC FVC PMVF PMSVC PMFVC
Adjust the speed display of C00.06.
V/F SVC FVC PMVF PMSVC PMFVC
Adjust the output power display of C00.10.
V/F SVC FVC PMVF PMSVC PMFVC
Unit: Reserved
Ten: C05 display selection
0: Automatically switch according to the control mode
1:VF mode related parameters
2: VC mode related parameters
Hundreds place: C00.40~C00.63 display selection
0: Do not display 1: display
Thousands: Communication fault code switching enable
0: not enabled
1: Enable, the fault code is switched to the same as AC300 when
485 communication
2: Enable, the fault code is switched to the AC70 when 485
communication
V/F SVC FVC PMVF PMSVC PMFVC
Unit: Output current display filter
0~F: the larger the value, the deeper the filter
V/F SVC FVC PMVF PMSVC PMFVC
Set the display selection when the motor is self-learning
0: Display self-learning process status 1: Do not display self-learning
process status
V/F SVC FVC PMVF PMSVC PMFVC
Unit: The fault is displayed when the fault recovers.
0: Do not display 1: Display
Content
V/F SVC FVC PMVF PMSVC PMFVC
0:Slave,1:Host
V/F SVC FVC PMVF PMSVC PMFVC
Set different values for different slaves.
V/F SVC FVC PMVF PMSVC PMFVC
0:1200 bps
1:2400 bps
3:9600 bps
4:19200 bps 5:38400 bps
6:57600 bps
V/F SVC FVC PMVF PMSVC PMFVC
0: (N, 8, 1) no parity, data bits: 8, stop bits: 1
1: (E, 8, 1) even parity, data bits: 8, stop bits: 1
2: (O, 8, 1) odd parity, data bits: 8, stop bits: 1
3: (N, 8, 2) no parity, data bits: 8, stop bits: 2
4: (E, 8, 2) even parity, data bits: 8, stop bits: 2
5: (O, 8, 2) odd parity, data bits: 8, stop bits: 2
37
2:4800 bps
Factory default
Adjustable
(range)
properly
0002
RUN
(0000 ~ 111F)
100.0%
RUN
(0.0~500.0%)
100.0%
RUN
(0.0~500.0%)
0000
RUN
(0000 ~ FFFF)
0002
RUN
(0000 ~000F)
0
STOP
(0 ~ 1)
0001
RUN
(0000 ~ 0001)
Factory default
Adjustable
(range)
properly
0
STOP
(0 ~ 1)
1
STOP
(1 ~ 247)
3
STOP
(0 ~ 6)
0
STOP
(0 ~ 5)