F07.46
Jump frequency 2
(0x072E)
F07.47
Jump frequency 2
(0x072F)
amplitude
4.11 F08:Auxiliary Control
Parameter
Name
(Address)
F08.00
Counter input source
(0x0800)
F08.01
Count input frequency
(0x0801)
division
F08.02
Counter maximum
(0x0802)
F08.03
Counter setting
(0x0803)
F08.04
Pulse number per
(0x0804)
meter
F08.05
Set length
(0x0805)
F08.06
Actual length
(0x0806)
F08.07
Timer time unit
(0x0807)
F08.08
Timer setting
(0x0808)
F08.3x:Swing Frequency Control
Parameter
Name
(Address)
F08.30
Swing frequency
(0x081E)
control
F08.31
Swing frequency
(0x081F)
amplitude control
yF08.32
Swing frequency
(0x0820)
preset frequency
Swing frequency
F08.33
preset frequency
(0x0821)
waiting time
F08.34
Swing frequency
(0x0822)
amplitude
F08.35
Kick frequency
(0x0823)
F08.36
Triangle wave rise time
(0x0824)
F08.37
Triangle wave fall time
(0x0825)
AC310 Series Frequency AC Drive Manual
V/F SVC FVC PMVF PMSVC PMFVC
Set the jump frequency 2
V/F SVC FVC PMVF PMSVC PMFVC
Set the amplitude of jump frequency 2
Content
V/F SVC FVC PMVF PMSVC PMFVC
0:normal X terminal 1:input PUL terminal 2~5:reserved
V/F SVC FVC PMVF PMSVC PMFVC
Set the input frequency division of the counter
V/F SVC FVC PMVF PMSVC PMFVC
Set the max value of the counter
V/F SVC FVC PMVF PMSVC PMFVC
Counter setting
V/F SVC FVC PMVF PMSVC PMFVC
Set the counter value for per meter
V/F SVC FVC PMVF PMSVC PMFVC
Set length
V/F SVC FVC PMVF PMSVC PMFVC
Set the actual length
V/F SVC FVC PMVF PMSVC PMFVC
Unit of the timer
0:Second
1:Minute
2:Hour
V/F SVC FVC PMVF PMSVC PMFVC
Set the timer setting
Content
V/F SVC FVC PMVF PMSVC PMFVC
0:Swing frequency control is invalid 1:Swing frequency control is
valid
V/F SVC FVC PMVF PMSVC PMFVC
Unit:Start Mode
0:Automatically
1:Terminal manual
Tens:Swing amplitude control
0: Relative center frequency 1:Relative maximum frequency.
Hundreds: preset frequency enable
0: not enabled 1: enabled
V/F SVC FVC PMVF PMSVC PMFVC
Set the swing frequency preset frequency
V/F SVC FVC PMVF PMSVC PMFVC
Set the swing frequency preset frequency waiting time
V/F SVC FVC PMVF PMSVC PMFVC
Set the swing frequency amplitude
V/F SVC FVC PMVF PMSVC PMFVC
Set the kick frequency
V/F SVC FVC PMVF PMSVC PMFVC
Set the triangle wave rise time
V/F SVC FVC PMVF PMSVC PMFVC
Set the triangle wave fall time
31
(0.00~Max
frequency)
0.00Hz
(0.00~Max
RUN
frequency)
0.00Hz
(0.00~Max
RUN
frequency)
Factory default
Adjustable
(range)
properly
0
RUN
(0 ~ 5)
0
RUN
(0 ~ 6000)
1000
RUN
(0 ~ 65000)
500
RUN
(0 ~ 65000)
10.0
RUN
(0.1~6500.0)
1000
STOP
(0 ~ 65000M)
0
STOP
(0 ~ 65000M)
0
STOP
(0 ~ 2)
0
STOP
(0 ~ 65000)
Factory default
Adjustable
(range)
properly
0
STOP
(0 ~ 1)
0000
STOP
(0000~0111)
0.00Hz
(0~upper limit
STOP
frequency)
0.0s
STOP
(0.0~3600.0s)
10.0%
STOP
(0.0~50.0%)
10.0%
STOP
(0.0~50.0%)
5.00s
STOP
(0.1~999.9s)
5.00s
STOP
(0.0~100.0s)

Advertisement

Table of Contents
loading

Table of Contents