Veichi AC310 Series Manual page 27

Frequency ac drive
Hide thumbs Also See for AC310 Series:
Table of Contents

Advertisement

●Communication control parameter group address description
Function Description
Communication given
frequency
Communication command
setting
AC Drive status
AC Drive fault code
Communication given upper
limit frequency
Communication torque setting
Torque control positive
maximum frequency limit
Torque control reverse
maximum frequency limit
Communication given PID set
value
Communication given PID
feedback value
Fault and warning code
reading
Output terminal status
AO output
Note: For other function code addresses, see the "Address" column in the function code profile
When using the writing command (06H) to write the F00~F15 parameters, if the function code parameter address field high nibble is 0, only write in the
AC Drive RAM, won't be stored when power down; if the function code parameter address field high nibble is 1, written in the EEPROM, and will be stored
when power down.
For example parameter F00.xx: 0x00xx (write in RAM), 0x10xx (stored in EEPROM); parameter F01.xx: 0x01xx (write in RAM) 0x11xx (stored in EEPROM), and so
on, for other parameters. When reading the F00~F15 parameter group parameters, the address high nibble is 0, such as reading the parameter F03.xx: 0x03xx.
When using the write command (06H) to write F16~F29 parameters, if the function code parameter address field high nibble is 5, only write in to the AC
AC310 Series Frequency AC Drive Manual
Address
Definition
0x3000 or 0x2000
0~32000 correspond to 0.00Hz~320.00Hz
0x0000:no command
0x0001:FWD run
0x3001 or 0x2001
0x0002:REV run
0x0003:FWD Jog
0x0004:REV Jog
Bit0
Bit1
Bit2
0x3002 or 0x2002
Bit3
Bit4
Bit5
Bit6
0x3003 or 0x2003
AC Drive current fault code (see fault code table)
0x3004 or 0x2004
0~32000 correspond to 0.00Hz~320.00Hz
0~1000 correspond to 0.0~100.0%
0x3005 or 0x2005
0x3006 or 0x2006
0~1000 correspond to 0.0~100.0%
0x3007 or 0x2007
0~1000 correspond to 0.0~100.0%
0x3008 or 0x2008
0~1000 correspond to 0.0~100.0%
0x3009 or 0x2009
0~1000 correspond to 0.0~100.0%
0x3010 or 0x2010
Fault code:0~127 Warning code:128 and above
External AC Drive output terminal,
Bit0 – Y
0x3018 or 0x2018
Bit1-- TA1-TB1-TC1;
Bit2 – extended Y1 (with IO expansion card)
BIT3 -- Extended relay (with IO expansion card)
0x3019 or 0x2019
0-10000 correspond to Output 0-10V/0-20mA
51
Slave address
Command code
Fault code
Low CRC CHK
High CRC CHK
Data meaning
0x0005:Dec stop
0x0006:free stop
0x0007:Fault reset
0x0008:Run prohibition
command
0x0009:Run permission
command
0:Stop status
1:Running status
0:Non-Acc
1:Acc status
status
0:Non-Dec
1:Dec status
status
0:Foward
1:Reverse
0:No fault
1:AC Drive fault
0:GPRS unlock
1:GPRS locked
1:AC
0:No warning
warning
01H
83H
04H
40H
F3H
Characteristics
W/R
W/R
R
Drive
R
W/R
W/R
W/R
W/R
W/R
W/R
R
R