Arameter - Veichi AC310 Series Manual

Frequency ac drive
Hide thumbs Also See for AC310 Series:
Table of Contents

Advertisement

F10.15
Energy consuming
(0x0A0F)
braking action voltage
F10.16
Bus undervoltage
(0x0A10)
suppression
F10.17
Bus undervoltage
(0x0A11)
suppression point
F10.18
Bus undervoltage
(0x0A12)
suppression gain
F10.19
Bus undervoltage
(0x0A13)
protection point
F10.2x:Auxiliary Protection
Parameter
Name
(Address)
F10.20
Input and output phase
(0x0A14)
loss protection options
F10.21
Input phase loss
(0x0A15)
threshold
F10.22
Ground short circuit
(0x0A16)
protection option
F10.23
Fan ON/OFF control
(0x0A17)
selection
F10.24
Fan control delay time
(0x0A18)
AC Drive overheating
F10.25
oH1 warning detection
(0x0A19)
level
AC310 Series Frequency AC Drive Manual
V/F SVC FVC PMVF PMSVC PMFVC
Set the energy consuming braking action voltage, when the bus
voltage is greater than this value, the energy consuming brake
starts to act
V/F SVC FVC PMVF PMSVC PMFVC
When the bus voltage is lower than the undervoltage suppression
point, the operating frequency is automatically adjusted to suppress
the bus voltage from decreasing, preventing the undervoltage fault.
0: off 1: on
V/F SVC FVC PMVF PMSVC PMFVC
Set bus voltage value for trigger undervoltage suppression function
V/F SVC FVC PMVF PMSVC PMFVC
Set the response effect of undervoltage suppression
V/F SVC FVC PMVF PMSVC PMFVC
Set the allowable lower limit of the bus voltage. Below this value, the
AC Drive reports undervoltage fault.
Content
V/F SVC FVC PMVF PMSVC PMFVC
Set whether the input and output phase loss protection functions are
enabled.
Unit: Output phase loss protection
0: off 1: on
Tens: input phase loss protection
0: off
1: On, when detect the input loss phase report warning
A.ILF, continue to run
2: On, when detect input loss phase report fault E.ILF, free stop
V/F SVC FVC PMVF PMSVC PMFVC
Set the percentage of voltage detection of the input phase loss
detection function, 100% corresponds to the rated bus voltage
V/F SVC FVC PMVF PMSVC PMFVC
Set whether the AC Drive output and the AC Drive cooling fan
ground short circuit protection function are enabled.
Unit: Output short circuit protection
0: off 1: on
Tens: fan to ground short circuit protection
0: off 1: on
V/F SVC FVC PMVF PMSVC PMFVC
Set the AC Drive cooling fan operation mode
0: The fan runs after the AC Drive is powered on.
1: After the shutdown, the fan operation is related to temperature,
and the operation is running.
2: After the shutdown, the fan stops after F10.24, and the operation
is related to temperature.
V/F SVC FVC PMVF PMSVC PMFVC
Set the time from shutdown to the cooling fan stops running
V/F SVC FVC PMVF PMSVC PMFVC
Set the temperature value of the AC Drive overheat warning, which
is highter than the value to report the overheat warning.
33
T3:735
S2:360
(0~ overvoltage point)
RUN
T3 overvoltage
point:820V;S2
overvoltage
point:390V
0
STOP
(0 ~ 1)
T3:430
S2:240
(0~ overvoltage point)
STOP
T3 overvoltage
point:820V;S2
overvoltage
point:390V
100.0%
RUN
(0.0~500.0%)
T3:350
S2:190
(0~ overvoltage point)
STOP
T3 overvoltage
point:820V;S2
overvoltage
point:390V
Factory default
Adjustable
(range)
properly
0021
STOP
(000 ~ 0121)
10%
STOP
(0 ~30.0%)
0011
STOP
(0000 ~0012)
1
RUN
(0~2)
30.00s
STOP
(0 ~600.00)
80.0℃
RUN
(0 ~100.0)