Parameter
Name
(Address)
F01.20
Acceleration/decelerati
(0x0114)
on time reference
F01.21
Acceleration time unit
(0x0115)
F01.22
Acceleration time 1
(0x0116)
F01.23
Deceleration time 1
(0x0117)
F01.24
Acceleration time 2
(0x0118)
F01.25
Deceleration time 2
(0x0119)
F01.26
Acceleration time 3
(0x011A)
F01.27
Deceleration time 3
(0x011B)
F01.28
Acceleration time 4
(0x011C)
F01.29
Deceleration time 4
(0x011D)
S curve acceleration
F01.30
and deceleration
(0x011E)
selection
F01.31
S curve acceleration
(0x011F)
start time
F01.32
S curve acceleration
(0x0120)
end time
F01.33
S curve deceleration
(0x0121)
start time
F01.34
S curve deceleration
(0x0122)
end time
Switching frequency
F01.35
between acceleration
(0x0123)
time 1 and acceleration
time 2
F01.4x:PWM Controlling
Parameter
Name
(Address)
F01.40
The carrier frequency
(0x0128)
AC310 Series Frequency AC Drive Manual
Content
V/F SVC FVC PMVF PMSVC PMFVC
Set
the
reference
frequency
acceleration/deceleration time.
0: Maximum frequency 1: Fixed frequency 50Hz 2: Set frequency
V/F SVC FVC PMVF PMSVC PMFVC
The unit of acceleration time setting.
0:1s
1:0.1s
2:0.01s
V/F SVC FVC PMVF PMSVC PMFVC
The time required for the output frequency to accelerate from 0.00
Hz to the reference frequency.
1~65000s(F01.21 = 0)
0.1~6500.0s(F01.21 = 1)
0.01~650.00s(F01.21 = 2)
V/F SVC FVC PMVF PMSVC PMFVC
Time required for the output frequency to decelerate from the
reference frequency to 0.00 Hz.
V/F SVC FVC PMVF PMSVC PMFVC
Time required for the output frequency to accelerate from 0.00Hz to
the reference frequency
V/F SVC FVC PMVF PMSVC PMFVC
Time required for the output frequency to decelerate from the
reference frequency to 0.00 Hz.
V/F SVC FVC PMVF PMSVC PMFVC
Time required for the output frequency to accelerate from 0.00Hz to
the reference frequency
V/F SVC FVC PMVF PMSVC PMFVC
Time required for the output frequency to decelerate from the
reference frequency to 0.00 Hz.
V/F SVC FVC PMVF PMSVC PMFVC
Time required for the output frequency to accelerate from 0.00Hz to
the reference frequency
V/F SVC FVC PMVF PMSVC PMFVC
Time required for the output frequency to decelerate from the
reference frequency to 0.00 Hz.
V/F SVC FVC PMVF PMSVC PMFVC
S curve acceleration and deceleration selection is valid or invalid
0:invalid 1:valid
V/F SVC FVC PMVF PMSVC PMFVC
Set the S curve acceleration start time.
V/F SVC FVC PMVF PMSVC PMFVC
Set the S curve acceleration end time
V/F SVC FVC PMVF PMSVC PMFVC
Set the S curve deceleration start time.
V/F SVC FVC PMVF PMSVC PMFVC
Set the S curve deceleration end time
V/F SVC FVC PMVF PMSVC PMFVC
Set the frequency switch between Acc time 1 and Acc time 2
Content
V/F SVC FVC PMVF PMSVC PMFVC
Use to set the switching frequency of the AC Drive IGBT.
15
Factory default
to
calculate
the
(0 ~ 2)
Model related (0.01 ~
650.00s)
Model related
(0.01~650.00s)
Model related
(0.01~650.00s)
Model related
(0.01~650.00s)
Model related
(0.01~650.00s)
Model related
(0.01~650.00s)
Model related
(0.01~650.00s)
Model related
(0.01~650.00s)
(0~1)
(0.00~10.00)
(0.00~10.00)
(0.00~10.00)
(0.00~10.00)
(0.00~Max
frequency)
Factory default
Model related (1.0~
16.0kHz)
Adjustable
(range)
properly
0
STOP
(0 ~ 2)
2
STOP
RUN
RUN
RUN
RUN
RUN
RUN
RUN
RUN
1
STOP
0.20s
STOP
0.20s
STOP
0.20s
STOP
0.20s
STOP
0.00Hz
RUN
Adjustable
(range)
properly
RUN