6 Setup

Function/Configuration
24
6
Setup
6.1

General information

The figures in brackets refer to the following illustrations.
In the basic setting, products with a density ≥ 0.7 g/cm³ (0.025 lbs/in³)
can be detected. For products with lower density, you have to set the
switch to ≥ 0.47 g/cm³ (0.017 lbs/in³).
Optionally the instrument can be supplied instead of ≥ 0.47 g/cm also
with a min. density range of ≥ 0.42 g/cm³ (0.015 lbs/in³).
On the electronics module you will find the following display and
adjustment elements:
Signal lamps (1, 2, 3)
DIL switch for mode setting - min./max. (4)
DIL switch for adjustment of the density range (5)
Test key (6)
Mode adjustment (min./max.)
On the controller SU 501 Ex, via the controller.
The switching condition can be changed with the min./max. switch.
You can set the required mode according to the "Function table" (max.
- max. detection or overfill protection, min. - min. detection or dry run
protection). The switching delay can also be modified on the controller
(SU 501 Ex controller).
If you want to carry out the mode adjustment via the controller, you
have to set the mode switch on the electronics module of OPTIS-
WITCH 5300 C to " max.".
Note:
Always immerse the tuning fork of OPTISWITCH 5300 C in a liquid to
test its function. Do not test the function of OPTISWITCH 5300 C with
your hand. This can damage the sensor.
OPTISWITCH 5300 C • Two-wire 8/16 mA