Adjustment Elements - KROHNE OPTISWITCH 5300 Handbook

Vibrating level switch
Hide thumbs Also See for OPTISWITCH 5300:
Table of Contents

Advertisement

Control lamp (1) - fault
indication (red)
Signal lamp (2) - Switch-
ing condition (yellow)
Signal lamp (3) - Operat-
ing condition (green)
OPTISWITCH 5300 C • Two-wire 8/16 mA
6.2

Adjustment elements

Fig. 14: Electronics module - Two-wire output
1
Signal lamp - red (LED)
2
Signal lamp - yellow (LED)
3
Signal lamp - green (LED)
4
DIL switch for mode adjustment
5
DIL switch for adjustment of the density range
6
Test key
The instrument monitors the vibrating frequency, electronics tempera-
ture and internal instrument functions.
Red LED lights = fault
Reaktion on the output
Control lamp for indication of the switching status.
With the mode setting (4), the switching condition and hence the
function of the signal lamp can be changed.
Yellow LED lights = 8 mA
Yellow LED off = 16 mA
Green LED lights = operating voltage on
2
3
4
1
6 Setup
5
6
25