Function/Configuration
OPTISWITCH 5300 C • - two-wire
6

Setup

6.1

General information

The figures in brackets refer to the following illustrations.
In the basic setting, products with a density ≥ 0.7 g/cm³ (0.025 lbs/in³)
can be detected. For products with lower density, you have to set the
switch to ≥ 0.47 g/cm³ (0.017 lbs/in³).
On the electronics module you will find the following display and
adjustment elements:
Signal lamps (1, 2, 3)
DIL switch for mode setting - min./max. (4)
DIL switch for sensitivity adjustment (5)
Test key (6)
Mode adjustment (min./max.)
On the signal conditioning instrument SU 501 Ex, via the signal condi-
tioning instrument.
The switching condition can be changed with the min./max. switch.
You can set the required mode according to the "Function chart"
(max. - max. detection or overfill protection, min. - min. detection or
dry run protection). The switching delay can also be modified on the
signal conditioning instrument (SU 501 Ex signal conditioning instru-
ment).
If you want to carry out the mode adjustment via the signal condition-
ing instruments, you have to set the mode switch on the electronics
module of OPTISWITCH 5300 C to "max.".
Note:
Always immerse the tuning fork of OPTISWITCH 5300 C in a liquid to
test its function. Do not test the function of OPTISWITCH 5300 C with
your hand. This can damage the sensor.