Proof Test (Whg, Sil) - KROHNE OPTISWITCH 5300 Handbook

Vibrating level switch
Hide thumbs Also See for OPTISWITCH 5300:
Table of Contents

Advertisement

Mode on the
Level
controller
Mode max.
Overflow pro-
tection
Mode max.
Overflow pro-
tection
mode min.
Dry run pro-
tection
mode min.
Dry run pro-
tection
Failure of the
any
supply volt-
age
Mode (max./
min.)
Fault message
any
Mode (max./
min.)
Implementation - Func-
tion test
OPTISWITCH 5300 C • Two-wire 8/16 mA
Sensor
Signal cur-
Signal lamp -
rent - Sensor
green
Voltage sup-
ply
approx. 8 mA
approx. 16 mA
approx. 8 mA
approx. 16 mA
-
approx.
3.6 mA
6.4

Proof test (WHG, SIL)

To find out possible undetected, dangerous failures, a proof test must
be carried out in adequate time intervals to check the safety function.
It is the user's responsibility to choose the type of testing.
You will find further instructions in the Safety Manual.
The following options are available for carrying out the proof test
(WHG, SIL):
1 Filling the vessel up to the switching point
If this does not cause any problems, you can fill the vessel up to the
switching point and monitor the correct sensor reaction.
2 Dismounting of the sensor and immersion in the original
medium
You can dismount the sensor for test purposes and check its proper
functioning by immersing it in the original product.
Signal lamp -
Signal lamp
yellow
- red
Switching
Fault mes-
status
sage
6 Setup
Controller
Analogue -
input control
> 3.8 mA
< 11.5 mA
> 12.5 mA
< 21 mA
> 3.8 mA
< 11.5 mA
> 12.5 mA
< 21 mA
-
≤ 3.6 mA
≥ 21 mA
27