Potential Equalization; Terminals; Cable Entries; Cable Specification - Endress+Hauser Proline Prosonic Flow P 500 Technical Information

Ultrasonic time-of-flight flowmeter
Hide thumbs Also See for Proline Prosonic Flow P 500:
Table of Contents

Advertisement

Proline Prosonic Flow P 500

Potential equalization

Terminals

Cable entries

Cable specification

5)
Endress+Hauser
Requirements
For potential equalization:
• Pay attention to in-house grounding concepts
• Take account of operating conditions like the pipe material and grounding
• Medium, Connect the sensor and transmitter to the same electric potential
• Use a ground cable with a minimum cross-section of 6 mm
potential equalization connections
Spring-loaded terminals: Suitable for strands and strands with ferrules.
Conductor cross-section 0.2 to 2.5 mm
• Cable gland: M20 × 1.5 with cable ⌀ 6 to 12 mm (0.24 to 0.47 in)
• Thread for cable entry:
• NPT ½"
• G ½"
• M20
• Device plug for digital communication: M12
Only available for certain device versions →  29.
Permitted temperature range
• The installation guidelines that apply in the country of installation must be observed.
• The cables must be suitable for the minimum and maximum temperatures to be expected.
Power supply cable (incl. conductor for the inner ground terminal)
Standard installation cable is sufficient.
Protective grounding cable for the outer ground terminal
Conductor cross-section < 2.1 mm
The use of a cable lug enables the connection of larger cross-sections.
The grounding impedance must be less than 2 Ω.
Signal cable
Current output 4 to 20 mA HART
A shielded cable is recommended. Observe grounding concept of the plant.
Modbus RS485
The EIA/TIA-485 standard specifies two types of cable (A and B) for the bus line which can be used
for every transmission rate. Cable type A is recommended.
Cable type
Characteristic impedance
Cable capacitance
Wire cross-section
Cable type
Loop resistance
Signal damping
Shield
Current output 0/4 to 20 mA
Standard installation cable is sufficient
2
(24 to 12 AWG).
2
(14 AWG)
A
135 to 165 Ω at a measuring frequency of 3 to 20 MHz
< 30 pF/m
> 0.34 mm
2
(22 AWG)
Twisted pairs
≤110 Ω/km
Max. 9 dB over the entire length of the cable cross-section
Copper braided shielding or braided shielding with foil shield. When grounding
the cable shield, observe the grounding concept of the plant.
5)
2
(10 AWG) and a cable lug for
37