Potential Equalization; Requirements; Special Connection Instructions; Connection Examples - Endress+Hauser Proline Prosonic Flow P 500 Operating Instructions Manual

Ultrasonic time-of-flight flowmeter hart
Hide thumbs Also See for Proline Prosonic Flow P 500:
Table of Contents

Advertisement

Proline Prosonic Flow P 500 HART
4)
Endress+Hauser
7.4

Potential equalization

7.4.1

Requirements

For potential equalization:
• Pay attention to in-house grounding concepts
• Take account of operating conditions like the pipe material and grounding
• Medium, Connect the sensor and transmitter to the same electric potential
• Use a ground cable with a minimum cross-section of 6 mm
for potential equalization connections
7.5

Special connection instructions

7.5.1

Connection examples

Current output 4 to 20 mA HART
1
 46
Connection example for 4 to 20 mA HART current output (active)
1
Automation system with current input (e.g. PLC)
2
Ground cable shield at one end. The cable shield must be grounded at both ends to comply with EMC
requirements; observe cable specifications →  202
3
Connection for HART operating devices →  82
4
Resistor for HART communication (≥ 250 Ω): observe maximum load →  196
5
Analog display unit: observe maximum load →  196
6
Transmitter
1
 47
Connection example for 4 to 20 mA HART current output (passive)
1
Automation system with current input (e.g. PLC)
2
Power supply
3
Ground cable shield at one end. The cable shield must be grounded at both ends to comply with EMC
requirements; observe cable specifications
4
Analog display unit: observe maximum load →  196
5
Transmitter
2
3
4
2
3
Electrical connection
2
(10 AWG) and a cable lug
4...20 mA
5
4
4...20 mA
4)
6
A0029055
5
A0028762
55