Helios AIR1-XVP 850 Installation And Operating Instructions Manual

Central ventilation units

Advertisement

Available languages

Available languages

Quick Links

Helios Ventilatoren
MONTAGE- UND BETRIEBSVORSCHRIFT
INSTALLATION AND OPERATING INSTRUCTIONS
NOTICE DE MONTAGE ET D'UTILISATION
Zentral-Lüftungsgeräte
Central ventilation units
Appareils de ventilation centrale
AIR1-XVP 850-3500
mit Kreuzgegenstrom-Wärmetauscher
with cross-counterflow heat exchanger
avec échangeur de chaleur à contre-courant transversal
DE
EN
FR

Advertisement

loading

Summary of Contents for Helios AIR1-XVP 850

  • Page 1 Helios Ventilatoren MONTAGE- UND BETRIEBSVORSCHRIFT INSTALLATION AND OPERATING INSTRUCTIONS NOTICE DE MONTAGE ET D’UTILISATION Zentral-Lüftungsgeräte Central ventilation units Appareils de ventilation centrale AIR1-XVP 850-3500 mit Kreuzgegenstrom-Wärmetauscher with cross-counterflow heat exchanger avec échangeur de chaleur à contre-courant transversal...
  • Page 2: Table Of Contents

    Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP DEUTSCH Inhaltsverzeichnis KAPITEL 1 ALLGEMEINE HINWEISE SEITE 2 Wichtige Informationen ............................Seite 2 Garantieansprüche – Haftungsausschluss ......................Seite 2 Vorschriften/Richtlinien ............................Seite 2 Einsatzbereich – Bestimmungsgemäße Verwendung ..................Seite 2 Warn- und Sicherheitshinweise ......................... Seite 2 KAPITEL 2 INSTALLATION UND INBETRIEBNAHME  SEITE 3 Allgemeine Montagehinweise ..........................
  • Page 3 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP KAPITEL 3 TECHNISCHE DATEN  SEITE 39 Technische Daten ............................Seite 39 Geräteübersicht .............................. Seite 40 Abmessungen ..............................Seite 41 Leistungskennlinien ............................Seite 42 KAPITEL 4 FUNKTIONEN UND EINSTELLUNGEN SEITE 42 Betriebsmodi ..............................Seite 42 4.1.1 Manueller Betrieb ............................
  • Page 4: Allgemeine Hinweise

    Wenn die nachfolgenden Ausführungen nicht beachtet werden, entfällt die Gewährleistung. Gleiches gilt für Haftungs- ansprüche an den Hersteller. Der Gebrauch von Zubehörteilen, die nicht von Helios empfohlen oder angeboten werden, ist nicht statthaft. Even tuell auftretende Schäden unterliegen nicht der Gewährleistung.
  • Page 5: Installation Und Inbetriebnahme

    Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP Die Anwendungsbeschränkungen der AIR1 XVP.. Geräte sind aus der folgenden Tabelle ersichtlich: AIR1 XVP AIR1 XVP AIR1 XVP AIR1 XVP AIR1 XVP 1250 1800 2500 3500 Umgebungstemperatur 0 - 50 °C 0 - 50 °C 0 - 50 °C 0 - 50 °C 0 - 50 °C...
  • Page 6: Transport

    Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP Schutz durch trockene, luft- und staubdichte Verpackung (Kunststoffbeutel mit Trockenmittel und Feuchtigkeitsindika- toren). Der Lagerort muss erschütterungsfrei, wassergeschützt und frei von übermäßigen Temperaturschwankungen sein. Schäden, deren Ursprung in unsachgemäßem Transport, unsachgemäßer Einlagerung oder Inbetriebnahme liegen, sind nachweisbar und unterliegen nicht der Gewährleistung.
  • Page 7: Feuerstätten

    Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP Wird das Gerät mit einem Kran transportiert, müssen die Transportrahmenlöcher im Grundrahmen verwendet werden (s. Abb.3). 1. Transportgestänge durch die Löcher im Grundrahmen führen. 2. Die Transportgestänge mit den Schrauben sicher befestigen. 3. Kette oder Seil bis zum Ende des Transportgestänges führen. 4.
  • Page 8: Entsorgung

    Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP 231 Entsorgung Lebensgefahr durch elektrischen Stromschlag! GEFAHR Ein elektrischer Stromschlag kann zu Tod oder schweren Verletzungen führen – Sicherstellen, dass das Gerät spannungsfrei und isoliert ist. Gerät erden und kurzschließen, benachbarte spannungs- führende Komponenten abschirmen. Alle Komponenten und Filter sowie ausgediente Betriebsmittel (z.B.
  • Page 9: Kondensatablauf

    Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP A: Mindestabstand für die Wartung oberhalb des Geräts B: Tiefe des Geräts C: Mindestabstand für die Wartung vor dem Gerät D: Höhe des Lüftungsgeräts (inkl. Klemmenkasten) Abb4 Type Maße (mm) A (mm) B (mm) C (mm) D (mm) AIR1 XVP 850 1085 1596...
  • Page 10 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP Kugelsiphon als Zubehör verfügbar. HINWEIS 1. Das Kondensatrohr wird im Folgenden dargestellt (s. Abb.6). Abb6 2. Den Rohrhalter befestigen (s. Abb.7). Abb7 3. Den Rohrbogen unter der Kondensatwanne befestigen. Sicherstellen, dass die Konstruktion wasserdicht ist, indem das Rohrverbindungsteil gedreht wird (s.
  • Page 11: Flanschanschluss / Anschlussstutzen

    Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP 4. Die Türen mit dem im Lieferumfang enthaltenen Schlüssel entriegeln und die Türen öffnen (s. Abb.9). Abb9 5. Den Kondensatverschluss mit einem Schraubendreher entfernen (s. Abb.10). Abb10 6. Den Kondensatverschluss von der Schraube lösen und die Schraube mit einem Schraubendreher festziehen (s. Abb.11).
  • Page 12: Luftführung, Lüftungsleitung

    Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP Abb14 Gerätetype Maße (mm) AIR1 XVP 2500 520 AIR1 XVP 3500 720 n: Anzahl der Bohrungen Loch-/Bolzenmaß: M8 x 16 – Den Kanal, das Übergangsstück und das flexible Kanalverbindungsstück in den Ecken des Geräts mit Schrauben HINWEIS M8 x 16 anschrauben (AIR1 XVP 2500/3500).
  • Page 13: Elektrischer Anschluss

    Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP 3. Den Filter einsetzen und verriegeln wie unten gezeigt (s. Abb.17). ACHTUNG Die Filterklasse muss im Inbetriebnahme-Assistent eingestellt werden (s. Kap. 2.11). Abb17 Elektrischer Anschluss Vor allen Wartungs- und Installationsarbeiten oder vor Öffnen des Klemmenkastens ist das Gerät allpolig vom GEFAHR Netz zu trennen! Der elektrische Anschluss darf nur von einer autorisierten Elektrofachkraft entsprechend den nachstehenden Anschlussplänen ausgeführt werden Der Elektroanschluss muss bis zur finalen Montage all-...
  • Page 14: Befestigung Und Anschluss Des Hauptschalters

    Der Hauptschalter ist Teil des Lieferumfangs und liegt dem Beipack bei (siehe Kap. 2.1.1 „Sendungsannahme“). Bei den Baureihen AIR1-XVP 850 - 1800 wird der Hauptschalter (➊) oben montiert. Bei den Baureihen AIR1-XVP 2500/3500 wird der Hauptschalter (➋) seitlich rechts oder links, an der Vorder-oder Rück- seite, montiert.
  • Page 15 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP 3. Das Hauptschaltergehäuse öffnen (s. Abb.21). Leitungsquerschnitt, der für den Stromanschluss verwendet wird, überprüfen. Abb21 4. Kabelverschraubung lösen und Leitung (Versorgungsleitung sowie Leitung von Hauptschalter zu Elektro-Anschluss- kasten im Gerät) durchführen. Leitungen an die Klemmen anschließen (s. Abb.22). Die Verbindungen sind dem Anschlussplan zu entnehmen.
  • Page 16: Anschluss Bedienelement

    Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP 2. Abdeckung des Klemmenkastens öffnen (s. Abb.25a). 3. Leitungsquerschnitt, der für den Stromanschluss verwendet wird, überprüfen (siehe Anschlussplan). 4. Netzleitung in das Gerät einführen (s. Abb.25b, c). Abb25     5. Kabel mit den markierten Anschlusspunkten verbinden (s. Anschlussplan). Abb26 293 Anschluss Bedienelement Lebensgefahr durch elektrischen Stromschlag!
  • Page 17: Modbus/Bacnet

    Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP 4. Das andere Ende der Leitung am Bedienelement anschließen (s. Anschlussplan). Abb29 AIR1 BE-ECO AIR1 BE-TOUCH 2 294 Modbus/Bacnet Die AIR1 XVP Lüftungsgeräte haben einen rs485-Anschluss und einen Ethernet-Anschluss. Der rs485-Anschluss wird für die interne Kommunikation der Drucksensoren verwendet. Der Ethernet-Anschluss kann für die Kommunikation mit der Gebäudeleittechnik verwendet werden.
  • Page 18: Anschlusspläne

    Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP 210 Anschlusspläne AIR1-XVP 850 Haupt-Anschlussplan SS-1506...
  • Page 19 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP AIR1-XVP 850 Elektrische Vorheizung/ Nachheizung SS-1516...
  • Page 20 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP AIR1-XVP 1250 Haupt-Anschlussplan SS-1507...
  • Page 21 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP AIR1-XVP 1250 Elektrische Vorheizung/ Nachheizung SS-1517...
  • Page 22 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP AIR1-XVP 1250 Elektrische Vorheizung SS-1518...
  • Page 23 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP AIR1-XVP 1800 Haupt-Anschlussplan SS-1508...
  • Page 24 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP AIR1-XVP 1800 Elektrische Vorheizung/ Nachheizung SS-1519...
  • Page 25 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP AIR1-XVP 2500 Haupt-Anschlussplan SS-1509...
  • Page 26 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP AIR1-XVP 2500 Elektrische Vorheizung/ Nachheizung SS-1520...
  • Page 27 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP AIR1-XVP 3500 Haupt-Anschlussplan SS-1510...
  • Page 28 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP AIR1-XVP 3500 Elektrische Vorheizung/ Nachheizung SS-1521...
  • Page 29: Inbetriebnahme-Assistent (Wizard)

    Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP Inbetriebnahme Assistent 211 Inbetriebnahme-Assistent (Wizard) Die wichtigsten Lüftungsgeräteeinstellungen können mit Hilfe des Inbetriebnahme-Assistenten (Wizard) vorgenommen werden (ausgenommen Einregulierung, Notfallbetrieb, Zeit/Datum, Schaltuhr). Das Bedienelement öffnet während der Erstinbetriebnahme automatisch den Inbetriebnahme-Assistenten und startet mit der Sprachauswahl. Falls die Einstellungen später geändert werden müssen (ausgenommen Sprachauswahl, Schaltuhr, Temperatur und Lüftungs-Sollwerte), muss der Inbetriebnahme-Assistent (Wizard) erneut aufgerufen werden.
  • Page 30: Aufrufen Des Inbetriebnahme-Assistenten (Wizard)

    Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP 2112 Aufrufen des Inbetriebnahme-Assistenten (Wizard) Schritt 1: Als Admin einloggen (Zugriffsrechte) ↑ Ventilatorregelung Schaltuhr → Zugriffsrechte ↓ → Einloggen Ausloggen Codeänderung Einloggen Code eingeben 1111 Ggw Bedienebene: Keine Schritt 2: Assistenten (Wizard) aktivieren Taste drücken, um zum Hauptmenü zurückzugelangen. Die Taste drücken, um zum Menü...
  • Page 31: Externe Regelung 0-10 V

    Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP Es kann nur ein Lüftungsgerät ausgewählt werden. Das Wort “Kein” erscheint automatisch in den anderen beiden Gruppen. Die letzte Einstellung ist gültig. ↑ AIR1 XVP Serie Wähle Gerätegröße ↓ Nicht zutreffend Gerät wählen: Beispiel: ↑...
  • Page 32 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP Beispiel: Außenlufttemperatur [°C] Zulufttemperatur [°C] ↑ Temperatur-Regel-Modus Außenl abh Zuluft-R ↓ Außenl abh Soll-Wer ↑ -20.0 °C = 25.0 °C -15.0 °C = 24.0 °C ↓ -10.0 °C = 23.0 °C Außenl abh Soll-Wer ↑...
  • Page 33 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP Der Sollwert wird im Menü „Temperatur“ angezeigt (als Benutzer oder Admin einloggen): ↑ Temperatur-Regel-Modus Abluft-Temp Kask-R ↓ ↑ Abluft-Temperatur Soll: XX.X °C ↓ e Außentemperaturabhängiges Umschalten zwischen Raum- und Zuluftregelung HINWEIS Nur mit dem als Zubehör erhältlichen Feuchte-Temperatur-Fühler AIR1/KWL-FTF 0-10V möglich. Den Analogausgang A2 (Temperatursignal) des AIR1/KWL-FTF 0-10V an den Analogeingang AI2 des Lüftungsgeräts anschließen (s.
  • Page 34 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP Die Raumtemperatur kann angepasst werden, wenn die Außentemperatur steigt. Zum Beispiel kann bei höheren Außentemperaturen eine etwas höhere Raumtemperatur akzeptabel sein, bzw. bei kühler Witterung eine etwas niedri- gere Raumtemperatur. Diese Funktion dient dem Energiesparen. Der Sollwert der Raumtemperatur wird außentemperaturabhängig mittels einer Regelungskurve mit 8 Punkten kom- pensiert.
  • Page 35: Lüftungsmodus

    Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP 2117 Lüftungsmodus Der Lüftungsmodus wird während der Inbetriebnahme festgelegt. Diese Einstellung kann später nur im Inbetriebnahme- Assistenten (Bedienebene Admin) verändert werden. Die folgenden Lüftungsmodi sind vorhanden: • Konstanter Volumenstrom • Konstante Drehzahl • Konstanter Druck •...
  • Page 36: Elektrische Vorheizung

    Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP c Konstanter Druck Nur mit dem als Zubehör erhältlichen Drucksensor AIR1-CAP möglich. Die Installation ist im Zuluft- oder im Abluftkanal HINWEIS möglich. Eine Lüftungsstufe ist möglich: • Normal Wird im späteren Betrieb die Lüftungsstufe minimal oder intensiv gewählt, läuft das Lüftungsgerät jeweils mit den Ein- stellungen für die Lüftungsstufe normal.
  • Page 37: Nachheizungstyp

    Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP • ePM1 55 % (F7) Eine entsprechende Filterdruckverlustkurve ist für jeden Filtertyp hinterlegt. Der Filter-/Wartungsalarm wird ausgelöst, wenn der Filterdruckverlust höher ist als zulässig, unabhängig vom gewählten Betriebspunkt. Nach dem Filterwechsel, schaltet der Alarm automatisch ab. ↑...
  • Page 38: Sensorgeführte Lüftung (Ventilation On Demand - Vod)

    Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP Taste drücken, um in das Menü „Außentemp-Bypass“ zu gelangen. Die Taste und die Taste drücken, um die oberen und unteren Grenzwerte der Außenlufttemperatur für die Nachtkühlung festzulegen. Bei Über- oder Unter- schreiten der Grenzwerte, wird der Bypassbetrieb automatisch beendet. Bypass aktiv zwischen ↑...
  • Page 39 Funktion deaktiviert. Der Brandmodus wird durch die Schließung des Schaltkontaktes DI2 aktiviert. Auswahl Normal offen Normal geschlossen 213 Einregulierung Die Einregulierung wird nach Abschluss des Inbetriebnahme-Assistenten im Hauptmenü durchgeführt. Sie erfolgt über das Untermenü „Ventilatorregelung“. Helios Ventilatoren 2019-XX-XX 09:30 System: Abgeschaltet SW: 19.5 Ist: 0.0 °C Betriebsmodus Temperatur Ventilatorregelung...
  • Page 40 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP Je nach gewählter Betriebsart („Konstanter Volumenstrom“, „Konstanter Druck“, „Konstante Drehzahl“) sind folgende Einstellungen vorzunehmen: a Konstant Volumenstrom • Volumenstromregelung ZV (Zuluftventilator) • Intensiv xxx [m³/h] • Normal xxx [m³/h] • Minimal xxx [m³/h] • Volumenstromregelung AV (Abluftventilator) •...
  • Page 41: Technische Daten

    Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP KAPITEL 3 Technische Daten TECHNISCHE Die mechanischen Verbindungen müssen korrekt ausgeführt sein, um den maximalen Wirkungsgrad des Geräts zu DATEN erreichen. Der thermische Wirkungsgrad, der Schallpegel und die elektrische Leistung des Geräts können je nach den Umgebungsbedingungen, unter denen das Gerät betrieben wird, variieren.
  • Page 42: Geräteübersicht

    Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP Geräteübersicht AIR1 XVP 850-1800 Abb30 AIR1 XVP 2500-3500 Abb31 Hauptschalter Außenluftvorfilter (ePM10 50% /optional) Fortluft Abluftfilter (ePM10 50%) Außenluft Warmwasser-/elektrische Nachheizung (optional) Abluft Bypassklappe Zuluft Kreuzgegenstrom-Wärmetauscher Durchführungen für Warmwasser-Nachheizung Abluft-/Fortluftventilator 17 16 Klemmenkasten Zuluft-/Außenluftventilator Elektrische Vorheizung Kondensatwanne Außenluftfilter (ePM1 55%)
  • Page 43: Abmessungen

    Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP Abmessungen AIR1-XVP 850- 1800 Abb32 ø32 ODA - Outdoor Air / Außenluft / Air extérieur EHA - Exhaust Air / Fortluft /Air rejeté ETA - Extract Air / Abluft / Air repris SUP - Supply Air / Zuluft / Air soufflé...
  • Page 44: Leistungskennlinien

    Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP Leistungskennlinien AIR1-XVP 850 AIR1-XVP 1250 Δp Δp V · (m³/h) V · (m³/h) 1000 1200 1400 750 1000 1250 1500 1750 2000 AIR1-XVP 1800 AIR1-XVP 2500 Δp Δp 1200 1000 V · (m³/h) V · (m³/h)
  • Page 45: Nachlauf

    Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP • Intensiv • Aus (Standby) Nach Auswahl der manuellen Betriebsart, lauft das Lüftungsgerät mit den eingestellten Sollwerten für die jeweilige Stufe. m Lebensgefahr durch elektrischenStromschlag! GEFAHR Ein elektrischer Stromschlag kann zu Tod oder schweren Verletzungen führen. Das Gerät steht auch nach der Auswahl „Aus“...
  • Page 46 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP Prioritäten der Schaltuhr (höchste Priorität zuerst): • Timer Intensiv • Timer Normal oder VOD (höherer Lüftungsbedarf) • Timer Minimal • Timer Umluftregelung Überschneiden sich die eingestellten Zeiten der Schaltuhren, z.B. wenn der Timer „Intensiv“ und der Timer „Normal“ für die gleiche Zeit programmiert werden, dann wird der Timer mit der höheren Priorität aktiviert und das Lüftungsgerät wird auf der Lüftungsstufe „Intensiv“...
  • Page 47 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP VOD Stoppzeit: Sobald das Lüftungsgerät auf der Lüftungsstufe „intensiv“ länger als 2 Stunden betrieben wurde, wird der sensorgeführte Betrieb für die eingestellte Nachlaufzeit beendet. 0 Stunden bedeutet, dass der sensorgeführte Betrieb aufgrund einer hohen Sensoranforderung nie beendet wird. →...
  • Page 48: Weitere Betriebseinstellungen

    Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP Festlegen der Nachlaufzeit: • Als Benutzer oder Admin einloggen • Das Menü „Schaltuhr“ aufrufen • Das Menü „Nachlauf“ aufrufen • Die gewünschte Nachlaufzeit festlegen Nachlauf XXX min Zeit in Nachlauf XXX min 416 Weitere Betriebseinstellungen Im Hauptmenü...
  • Page 49: Warmwasser-Heizregister-Frostschutz

    Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP • Stetige Leistungsregelung der Vorheizung bis eine Fortlufttemperatur von +4 °C oder 100 % der Leistung erreicht wird. • Sobald die Vorheizung für mehr als 3 Minuten mit einer Leistung von 100 % angesteuert wird, reduziert sich der Gesamtvolumenstrom (Zu- und Abluft) stetig um max.
  • Page 50: Prioritäten

    Tastendruck, stellen sich alle Benutzerebenen automatisch auf „Keine Rechte” zurück. Alle Passwörter können im Menü „Zugriffsrechte“ unter „Code ändern“ geändert werden. Wurde das Admin-Passwort geändert und dann vergessen, kann ein temporäres Master-Passwort von Helios angefor- dert werden (Helios Kundendienst).
  • Page 51: Menü-Übersicht Air1-Be Eco

    Montage- und Betriebsvorschrift Hauptmenü Zentral-Lüftungsgeräte AIR1 XVP Helios Ventilatoren AIR1 XVP 850 Programm Lüft.system EXOreal C Version Choose Language 2023-06-22 09:30 Cross Counter Flow U Version: 3.7-0-51 3.5-1-04 Sprachauswahl System: Gestoppt 2023-04-16 SVN Build German SW: 20.0 Ist: 0.0°C ID Nr: 011902011871 4364 Hauptmenü...
  • Page 52 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP Die Untermenüs vom Hauptmenü (Teil 2 von 2) 7. Eingänge / Ausgänge 9. Einstellungen AI1: 0.0 Inaktiv Temp.regelung Zuluftregelung AI Erweit 3 AI2: 45.5 Feuchte Volumenstromregl P-Band: 33.0 °C AI Erweit 4 AI3: 0.0 Inaktiv Alarmeinstellungen I-Zeit: 100.0 s AI4: 0.0 Inaktiv...
  • Page 53 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP Die Untermenüs von Konfiguration (Teil 1 von 4) System Kommunikation Umluftregelung Choose Language Erweiterungseinh 1 Temp.regl bei Konstanter oder Kommunikationsport1 Sprachauswahl Keine Umluft Offset-Sollwert Erw und FU/Druck German Erweiterungseinh 2 erlauben: bei Umluft Keine Heizen &...
  • Page 54 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP Die Untermenüs von Konfiguration (Teil 2 von 4) Eingänge / Ausgänge Sensoreinstell AI1: Zuluftdruck bei AI1... AI Erweit 3 Sign: Inaktiv 0.0V: 0.0 AI Erweit 4 Rohwert: NaN 10.0V: 500.0 Pa Fühlerkorr: 0.0 Filterfaktor: 0.2 Pressure A Erweit 3 Abluftdruck bei UI Erweit 3...
  • Page 55 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP Die Untermenüs von Konfiguration (Teil 3 von 4) ü Pumpensteuerung Funktion BSK: Freie Nachtkühl P1-Erhitzer Pumpenstopp: Ja Inaktiv Aktiv: Ja P1-WRG Ausschaltverz: 1 Min Betrieb bei Alarm Außentemp aktiv P1-Kühler Außent Stop: 0°C Gestoppt 22 °C Differenz: 1.0 Ventilatorstufe bei...
  • Page 56 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP Die Untermenüs von Konfiguration (Teil 4 von 4) Stufenregler fi Stufenregl Erhitz Stufenregl Erhitz Start Stufe 1: 10 % Alarm Nr(1-125): 1 Fehler Zuluftventila Verzögerung Stufenregl Kühler Sequentiell Stopp Stufe 1: 5 % Fehler Zuluftventila Priorität: B-Alarm Zuluftventilator Start Stufe 2: 45 %...
  • Page 57: Service Und Wartung

    Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP KAPITEL 5 Service und Wartung SERVICE UND Der Filterwechsel erfolgt in der Regel durch den Anwender. Zusätzliche Reinigungs- und Wartungsarbeiten dürfen nur WARTUNG von einer Elektrofachkraft durchgeführt werden. Lebensgefahr durch elektrischen Stromschlag! Vor allen Wartungs- und Installationsarbeiten sowie vor Öffnen des Klemmenkastens ist das Gerät allpolig vom GEFAHR Netz zu trennen! Gefährdung durch elektrischen Stromschlag, bewegliche Teile (Ventilatoren) und ggf heiße Oberflächen von...
  • Page 58: Service Und Wartung Des Kreuzgegenstrom-Wärmetauschers

    Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP Service und Wartung des Kreuzgegenstrom-Wärmetauschers Lebensgefahr durch elektrischen Stromschlag! GEFAHR Vor allen Wartungs- und Installationsarbeiten sowie vor Öffnen des Klemmenkasten ist das Gerät allpolig vom Netz zu trennen! Gefährdung durch elektrischen Stromschlag, bewegliche Teile (Gebläse) und heiße Oberflächen Verletzungsgefahr! WARNUNG Wärmetauscher haben ein hohes Gewicht und können Kondensatwasser enthalten!
  • Page 59: Reinigung Des Kreuzgegenstrom-Wärmetauschers

    Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP 3. Das Profil sorgfältig entfernen (s. Abb.38). Abb38 4. Den Wärmetauscher demontieren (s. Abb.39). Abb39 5. Die Klappen entfernen (s. Abb.40). Abb40 532 Reinigung des Kreuzgegenstrom-Wärmetauschers Der Kreuzgegenstrom-Wärmetauscher muss regelmäßig auf Schmutz und Staubablagerungen überprüft werden. Zusätzlich muss der Kreuzgegenstrom-Wärmetauscher alle 6 Monate auf Schäden überprüft werden.
  • Page 60: Service Und Wartung Der Ventilatoren

    Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP Die technischen Daten der Standard-Filter sind in der Tabelle ersichtlich: Filter Nenn-Luft- Anzahl Filterklasse Abmessungen Empfohlene volumen- Filter (LxHxB) (mm) Enddruck- strom (m³/h) differenz (Pa) AIR1 XVP 850 Abluftfilter ePM10 50 % 312 x 678 x 96 AIR1 XVP 850 Außenluftfilter ePM1 55 % 312 x 678 x 96...
  • Page 61: Reinigung Der Kondensatwanne

    Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP Der Ventilator muss alle 6 Monate auf Schmutz, Schäden und Korrosion überprüft werden: – Regelmäßige Inspektion, ggf. mit periodischer Reinigung ist erforderlich, um Unwucht durch Verschmutzung zu ver- meiden. – Das Ventilatorgehäuse reinigen. – Vibrations- und schwingungsfreier Betrieb sind zu gewährleisten. –...
  • Page 62: Reinigung Der Gehäuse

    Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP Kondensatwanne mit einem Tuch reinigen (s. Abb.47). Abb47 Reinigung der Gehäuse Lebensgefahr durch elektrischen Stromschlag! GEFAHR Vor allen Wartungs- und Reinigungsarbeiten das Gerät allpolig vom Stromnetz trennen Verletzungsgefahr durch elektrischen Schlag, bewegliche Teile (Gebläse) und heiße Oberflächen –...
  • Page 63: Alarme

    Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP h Funktionen Außenluftklappe • Auto = Die Außenluftklappe wird automatisch vom Regler geöffnet und geschlossen, wie im normalen Betrieb des Lüftungsgeräts. • Schließen = Die Außenluftklappe wird nicht angesteuert und schließt über Federrücklauf. • Öffnen = Die Außenluftklappe wird angesteuert und öffnet. i Funktionen Fortluftklappe •...
  • Page 64 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP Alarm Priorität Stopp Alarmbeschreibung und -behandlung Alarme Temperatur Fehler Zuluftregelung Nein • Differenz SOLL-/IST-Temperatur ist für 30 Minuten größer als 5 K • Sollwert ist unrealistisch prüfen • Optionale Heizung/Kühlregister prüfen • Mischer der optionalen Hydraulikeinheit prüfen •...
  • Page 65 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP Alarm Priorität Stopp Alarmbeschreibung und -behandlung Hand P1 Wärmetauscher Nein • Pumpe Wärmetauscher • Steuerung über Betriebsmodus manuell Hand P1 Kühler Nein • Pumpe Kaltwasser-Kühlregister • Steuerung über Betriebsmodus manuell Handbetrieb Extra Sequenz Y4 Nein •...
  • Page 66: Zubehör

    • Kühler prüfen • Verdrahtung prüfen Fehler P1 Wärmetauscher Nein • Wärmetauscher prüfen • Verdrahtung prüfen 510 Zubehör Für das Zubehör siehe die jeweiligen Bedienungsanleitungen. Zubehör (AIR1-XVP 850 - 3500) Bestell-Nr Bedienelement 40751 AIR1-BE TOUCH 2 AIR1-BE ECO Bedienelement 06186 Erweiterungskit für...
  • Page 67 Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP Zubehör (AIR1-XVP 850) Bestell-Nr ELF-AIR1 XVP 850/ePM10 50%/48 Vorfilter Außenluft 40515 ELF-AIR1 XVP 850/ePM11 80%/96 Filter Außenluft 40517 AIR1-EVH XVP 850 Elektrische Vorheizung (Schütz) 40473 Elektrische Nachheizung (Schütz) 40474 AIR1-ENH XVP 850 AIR1-NH WW XVP 850...
  • Page 68: Stilllegen Und Entsorgung

    Montage- und Betriebsvorschrift Zentral-Lüftungsgeräte AIR1 XVP Zubehör (AIR1-XVP 3500) Bestell-Nr ELF-AIR1 XVP 3500/ePM10 50%/48 Vorfilter Außenluft 40531 ELF-AIR1 XVP 3500/ePM11 80%/96 Filter Außenluft 40533 AIR1-EVH XVP 3500 Elektrische Vorheizung (Schütz) 40507 AIR1-ENH XVP 3500 Elektrische Nachheizung (Schütz) 40508 AIR1-NH WW XVP 3500 Warmwasser Nachheizung (Ventil) 40509 AIR1-KR KW XVP 3500 L...
  • Page 69: Konformitätserklärung

    EU Declaration of Conformity to EC Machinery Directive 2006/42/EC Annex II Part 1A / Déclaration de conformité UE selon la Directive CE relative aux machines 2006/42 Note II Partie 1A Helios Ventilatoren GmbH + Co KG Lupfenstr. 8, D-78056 Villingen-Schwenningen Hiermit erklären wir, dass die Produkte in Übereinstimmung mit den untenstehenden Richtlinien entwickelt,...
  • Page 70 Installation and Operating Instructions Central ventilation units AIR1 XVP ENGLISH Table of Contents CHAPTER 1 GENERAL INFORMATION  PAGE 2 Important information ............................Page 2 Waranty claims– Exclusion of liability ........................Page 2 Regulations - Guidelines ............................. Page 2 Area of application – Intended use........................Page 2 Warning and safety instructions .........................
  • Page 71 Installation and Operating Instructions Central ventilation units AIR1 XVP CHAPTER 3 TECHNICAL DATA  PAGE 38 Performance and technical data ........................Page 38 Unit overview ..............................Page 39 Dimensions ..............................Page 40 Performance curves ............................Page 41 Operating modes ............................Page 41 CHAPTER 4 FUNCTIONS AND SETTINGS  PAGE 41 4.1.1 Manual operation ............................
  • Page 72: Chapter 1 General Information

    If the preceding instructions are not observed, all warranty claims shall be excluded. This also applies for liability claims against the manufacturer. The use of accessories, which are not recommended or offered by Helios, is not permitted. Any possible damages are not covered by the warranty.
  • Page 73: Chapter 2 Installation And Commissioning

    Installation and Operating Instructions Central ventilation units AIR1 XVP The AIR1 XVP.. unit application limits can be seen in the following table:: AIR1 XVP AIR1 XVP AIR1 XVP AIR1 XVP AIR1 XVP 1250 1800 2500 3500 Ambient temperature 0 - 50 °C 0 - 50 °C 0 - 50 °C 0 - 50 °C...
  • Page 74: Shipping

    Installation and Operating Instructions Central ventilation units AIR1 XVP Shipping The shipping must be carried out carefully. It is recommended to leave the unit in the original packaging until installation to avoid possible damages and contamination. The shipping must be carried out by trained and experienced personnel and the necessary safety precautions should be taken to prevent overturning and slipping of the device.
  • Page 75: Disassembly And Re-Assembly

    Installation and Operating Instructions Central ventilation units AIR1 XVP 4. The spacers are used to prevent damage to the unit which could be caused by chains or ropes (see Fig.3). Fig3 Ø30 mm Risk of personal injury and material damage! DANGER The package units may have an eccentric centre of gravity If the package unit is incorrectly lifted, it can tip over Falling or tipping package units can cause serious personal injury...
  • Page 76: Mechanical Assembly

    Installation and Operating Instructions Central ventilation units AIR1 XVP batteries and accumulators. You can return batteries and accumulators free of charge to retailers or municipal collection points. Batteries or rechargeable batteries that contain harmful substances are marked with a crossed-out dustbin symbol. Under the garbage can symbol is the chemical designation of the pollutant.
  • Page 77: Leveling The Unit

    Installation and Operating Instructions Central ventilation units AIR1 XVP Leveling the unit The units AIR1 XVP.. units have adjustable levelling feet. It must be ensured that the unit is standing on a flat floor surface prior to installation work. The height of the levelling feet must be adjusted to level the unit. The height “H” must not exceed 125 mm (see Fig.5).
  • Page 78 Installation and Operating Instructions Central ventilation units AIR1 XVP 3. Fix the pipe bend below the condensation tray. Ensure that the construction is water-tight by turning the pipe con- nector (see Fig.8). Fig8 4. Unlock and open the doors with the key included in the scope of delivery (see Fig.9). Fig9 5.
  • Page 79: Flange Connection / Adapters

    Installation and Operating Instructions Central ventilation units AIR1 XVP Flange connection / adapters Ventilation units AIR1 XVP 850/1200/1800 have round adapters (Fig.12). Ventilation units AIR1 XVP 2500/3500 have rectangular adapters (Fig.13). Fig12 Fig13 Type Q Ø (mm) Type O (mm) P (mm) AIR1 XVP 850 AIR1 XVP 2500...
  • Page 80: Electrical Connection

    Installation and Operating Instructions Central ventilation units AIR1 XVP 2. Remove the screws from the filter rails, set the filter rails upwards and fasten in the in the threaded rivets (see Fig.16). Fig16     3. Insert and lock the filter as shown below (see Fig.17). ATTENTION The filter class must be adjusted in the commissioning assistant (see chap.
  • Page 81 The main switch is part of the scope of delivery and is included in the accessory pack (see chap. 2.1.1 “„Receipt“” For series AIR1-XVP 850 - 1800, the main switch (➊) is mounted on top. For series AIR1-XVP 2500/3500, the main switch (➋) is side-mounted on the right or left, on the front or rear.
  • Page 82 Installation and Operating Instructions Central ventilation units AIR1 XVP 2. Fix main switch to the panel or side of the housing with the screw M4x10 (see Fig.20). Fig20 3. Open the main switch housing (see Fig.21). Check the thickness of the cable to be used for power connection. Fig21 4.
  • Page 83: Controler Connection

    Installation and Operating Instructions Central ventilation units AIR1 XVP 2. Open the terminal box cover (see Fig.25a). 3. Check the thickness of the cable to be used for power connection (see wiring diagram). 4. Insert the power cable into the unit (see Fig.25b, c). Fig25 ...
  • Page 84: Connection Of Optional Air Quality Sensors

    Installation and Operating Instructions Central ventilation units AIR1 XVP 4. Connect the other end of the HMI cable to the display (see wiring diagram). Fig29 AIR1 BE-ECO AIR1 BE-TOUCH 2 294 Modbus/Bacnet AIR1 XVP.. units have a rs485 connection and Ethernet connection. The rs485 connection is used for the internal com- munication of the pressure sensors.
  • Page 85: Wiring Diagrams

    Installation and Operating Instructions Central ventilation units AIR1 XVP 210 Wiring diagrams AIR1-XVP 850 Main wiring diagram SS-1506...
  • Page 86 Installation and Operating Instructions Central ventilation units AIR1 XVP AIR1-XVP 850 Electrical preheater/ afterheater SS-1516...
  • Page 87 Installation and Operating Instructions Central ventilation units AIR1 XVP AIR1-XVP 1250 Main wiring diagram SS-1507...
  • Page 88 Installation and Operating Instructions Central ventilation units AIR1 XVP AIR1-XVP 1250 Electrical preheater/ afterheater SS-1517...
  • Page 89 Installation and Operating Instructions Central ventilation units AIR1 XVP AIR1-XVP 1250 Electrical preheater SS-1518...
  • Page 90 Installation and Operating Instructions Central ventilation units AIR1 XVP AIR1-XVP 1800 Main wiring diagram SS-1508...
  • Page 91 Installation and Operating Instructions Central ventilation units AIR1 XVP AIR1-XVP 1800 Electrical preheater/ afterheater SS-1519...
  • Page 92 Installation and Operating Instructions Central ventilation units AIR1 XVP AIR1-XVP 2500 Main wiring diagram SS-1509...
  • Page 93 Installation and Operating Instructions Central ventilation units AIR1 XVP AIR1-XVP 2500 Electrical preheater/ afterheater SS-1520...
  • Page 94 Installation and Operating Instructions Central ventilation units AIR1 XVP AIR1-XVP 3500 Main wiring diagram SS-1510...
  • Page 95 Installation and Operating Instructions Central ventilation units AIR1 XVP AIR1-XVP 3500 Electrical preheater/ afterheater SS-1521...
  • Page 96: Commissioning Assistant (Wizard)

    Installation and Operating Instructions Central ventilation units AIR1 XVP Inbetriebnahme Assistent 211 Commissioning assistant (wizard) The most important ventilation unit settings can be adjusted using the commissioning assistant (wizard) (except for adjustment, emergency operation, time/date, timer). The controller will automatically open the commissioning assistant during the initial commissioning and starts with the language selection.
  • Page 97: Calling Up The Commissioning Assistant (Wizard)

    Installation and Operating Instructions Central ventilation units AIR1 XVP 2112 Calling up the commissioning assistant (wizard) Step 1: Log in as Admin (Access rights) ↑ Fan control Timer → Access rights ↓ → Log on Log off Change password Log on Enter password 1111 Actual level: None Step 2: Activate assistant (wizard)
  • Page 98: Unit Selection

    Installation and Operating Instructions Central ventilation units AIR1 XVP 2114 Unit selection Selection of the applicable ventilation units: → • Central ventilation units AIR1 XVP.. AIR1 XVP Serie Only one ventilation unit can be selected. The word “None” appears automatically in the other two windows. The last setting is valid.
  • Page 99 Installation and Operating Instructions Central ventilation units AIR1 XVP b Outdoor Compensated Supply Air Control The supply air temperature setpoint can be set to improve the regulation of room heat losses due to the outdoor tem- perature. This ensures that the cooling of room walls is compensated for during the cold season. The supply air temperature setpoint is compensated for depending on the outdoor temperature using a control curve with 8 points.
  • Page 100 Installation and Operating Instructions Central ventilation units AIR1 XVP ↑ Temp. control mode Cascade extract ctrl ↓ ↑ Extract air temp. Setp: XX.X °C ↓ e Outdoor Temperature Dependent Supply or Room Temperature Control NOTE Only possible with the humidity-temp. sensor AIR1/KWL-FTF 0-10V accessory. Connect the analogue output A2 (temp.
  • Page 101 Installation and Operating Instructions Central ventilation units AIR1 XVP The room temperature can be adapted when the outside temperature rises. For example, a slightly higher room tem- perature may be acceptable at higher outside temperatures, or a slightly lower room temperature in cooler weather conditions.
  • Page 102: Ventilation Mode

    Installation and Operating Instructions Central ventilation units AIR1 XVP h Outdoor Temperature Dependent Extract Air Control The extract air temperature can be adapted when the outside temperature rises. For example, a slightly higher extract air temperature may be acceptable at higher outside temperatures, or a slightly lower extract air temperature in cooler weather conditions.
  • Page 103: Electrical Pre-Heating

    Installation and Operating Instructions Central ventilation units AIR1 XVP When setting the ventilation stage „minimal“, please observe the minimum volume flow For minimum flow see NOTE table „Performance and technical data“, chapter 31 b Constant speed 3 ventilation stages are available: •...
  • Page 104: Filter Type Extract Air

    Installation and Operating Instructions Central ventilation units AIR1 XVP The filter/maintenance alarm is triggered if the filter pressure loss is higher than the maximum permissible filter pressure loss, regardless of the selected operating point. The alarm will automatically deactivate after the filter change. ↑...
  • Page 105: Sensor-Controlled Ventilation (Ventilation On Demand - Vod)

    Installation and Operating Instructions Central ventilation units AIR1 XVP Press the button in the “Active above outside temp.” menu, to set the outside air temp. setpoint for the night cooling. Night cooling is only active if the intake air temperature was above this value during the last operation. Then press the button to set the temperature.
  • Page 106 Normally closed 213 Adjustment The adjustment is carried out in the main menu after completing the commissioning assistant. It is carried out under the submenu “Fan control”. Helios Ventilatoren 2019-XX-XX 09:30 System: Deactivated Target: 19.5 Actual: 0.0 °C Operating mode...
  • Page 107 Installation and Operating Instructions Central ventilation units AIR1 XVP Depending on the selected operating mode (“Constant volume flow”, “Constant pressure”, “Constant speed”), the following settings can be adjusted: a Constant volume flow • Volume flow regulation SAF (supply air fan) •...
  • Page 108: Performance And Technical Data

    Installation and Operating Instructions Central ventilation units AIR1 XVP CHAPTER 3 Performance and technical data TECHNICAL DATA Mechanical connections must be made correctly in order to achieve the maximum unit efficiency. The thermal efficiency, sound level and electrical performance of the unit may vary depending on the environmental conditions under which the unit is operated.
  • Page 109: Unit Overview

    Installation and Operating Instructions Central ventilation units AIR1 XVP Unit overview AIR1 XVP 850-1800 Fig30 AIR1 XVP 2500-3500 Fig31 Main switch Outside air pre-filter (ePM10 50% /optional) Exhaust air Extract air filter (ePM10 50%) Outside air Warm water/electrical auxiliary heater (optional) Extract air Bypass damper Supply air...
  • Page 110: Dimensions

    Installation and Operating Instructions Central ventilation units AIR1 XVP Dimensions AIR1-XVP 850- 1800 Fig32 ø32 ODA - Outdoor Air / Außenluft / Air extérieur EHA - Exhaust Air / Fortluft /Air rejeté ETA - Extract Air / Abluft / Air repris SUP - Supply Air / Zuluft / Air soufflé...
  • Page 111: Performance Curves

    Installation and Operating Instructions Central ventilation units AIR1 XVP Performance curves AIR1-XVP 850 AIR1-XVP 1250 Δp Δp V · (m³/h) V · (m³/h) 1000 1200 1400 750 1000 1250 1500 1750 2000 AIR1-XVP 1800 AIR1-XVP 2500 Δp Δp 1200 1000 V ·...
  • Page 112: Timer

    Installation and Operating Instructions Central ventilation units AIR1 XVP 411 Manual operation Selection options “Manual operation”: • Reduced • Normal • Boost • Off (Standby) After selecting manual operation mode, the ventilation unit will run with the adjusted setpoints for the respective stage. Danger to life due to electric shock! DANGER An electric shock can result in death or serious injury...
  • Page 113: Sensor-Controlled Operation (Vod - Ventilation On Demand)

    Installation and Operating Instructions Central ventilation units AIR1 XVP Timer priorities (highest priority first): • Timer Boost • Timer Normal or VOD (higher ventilation requirement) • Timer Reduced • Timer Recirculation If the set timer times overlap, e.g. if the “Boost” timer and the “Normal” timer are programmed for the same time, the timer with the higher priority will be activated and the ventilation unit will be operated at the “Boost”...
  • Page 114: Overrun

    Installation and Operating Instructions Central ventilation units AIR1 XVP VOD stop time: As soon as the ventilation unit has been operating at the “boost” ventilation stage for longer than 2 hours, the sensor-controlled operation will stop for the set overrun time. 0 hours means that the sensor-controlled ope- ration will not stop due to a high sensor requirement.
  • Page 115: Additional Operating Settings

    Installation and Operating Instructions Central ventilation units AIR1 XVP Adjustment of overrun time: • Log on as User or Admin • Call up the “Timer” menu • Call up the “Overrun” menu • Set the desired overrun time Overrun XXX min Time in overrun XXX min 416 Additional operating settings...
  • Page 116: Warm Water Heating Register Frost Protection

    Installation and Operating Instructions Central ventilation units AIR1 XVP • If the preheater runs for more than 5 minutes at a power of 100 %, the ventilation unit goes into stand-by mode (out- side dampers close) and an alarm message appears, which must be reset manually to restart the unit. Ventilation unit without preheater and with afterheater: An afterheater is available as an optional accessory.
  • Page 117: Priorities

    5 minutes from the last press of a button. All passwords can be modified in the “Access rights” menu under “Change password”. If the Admin password was modified and then forgotten, a temporary master password can be requested from Helios (Helios customer services).
  • Page 118: Menu Overview Air1-Be Eco

    Installation and Operating Instructions Main menu Central ventilation units AIR1 XVP Helios Ventilatoren AIR1 XVP 850 Programm vent.system EXOreal C Version Choose Language 2023-06-22 09:30 Cross Counter Flow U Version: 3.7-0-51 3.5-1-04 German System: stopped 2023-04-16 SVN Build Menu overview AIR1-BE Eco Main menu SP: 20.0 Act: 0.0°C...
  • Page 119 Installation and Operating Instructions Central ventilation units AIR1 XVP The submenus of the main menu (Part 2 of 2) 7. Inputs / Outputs 9. Settings AI1: 0.0 Not used Control temp Supply air control AI exp3 AI2: 45.5 Humidity Control flow P-band: 33.0 °C AI exp4 AI3: 0.0 Not used...
  • Page 120 Installation and Operating Instructions Central ventilation units AIR1 XVP The submenus of configuration (Part 1 of 4) System Communication Recirculation Choose Language Expansion unit1 Enable temp Constant or function port1 English None control when setpoint offset Exp and freq/press Expansion unit2 recirculation when recirculation: None...
  • Page 121 Installation and Operating Instructions Central ventilation units AIR1 XVP The submenus of configuration (Part 2 of 4) Inputs / Outputs Sensor settings AI1: SAF pressure at AI1... AI exp3 Sign: Not used 0.0V: 0.0 AI exp4 Raw value: NaN 10.0V: 500.0 Pa Comepnsation: 0.0 Filter factor: 0.2 Pressure A exp3...
  • Page 122 Installation and Operating Instructions Central ventilation units AIR1 XVP The submenus of configuration (Part 3 of 4) Fire function Free cooling Pump control Fire damper function: Free cool P1 heating Pump stop: Yes Not active active: Yes P1 exchanger Stop delay: 1 Min Operation when alarm Outd temp activation P1 cooling...
  • Page 123 Installation and Operating Instructions Central ventilation units AIR1 XVP The submenus of configuration (Part 4 of 4) Step controllers Alarm settings Other parameters Step contr heating Step contr heating Start step1: 10 % Alarm no(1-125): 1 Malfunction supply a Delay SAF Step contr cooling Sequential Stop step1: 5 %...
  • Page 124: Chapter 5 Service And Maintenance

    Installation and Operating Instructions Central ventilation units AIR1 XVP CHAPTER 5 Service and maintenance SERVICE AND The filter change is usually carried out by the user. Additional cleaning and maintenance work may only be carried out MAINTENANCE by an electrician. Danger to life! due to electric shock! DANGER The unit must be fully isolated from the mains power supply before all maintenance and installation work and...
  • Page 125 Installation and Operating Instructions Central ventilation units AIR1 XVP Service and maintenance of cross counterflow heat exchanger Danger to life! The unit must be fully isolated from the mains power supply before all maintenance and installation work and DANGER opening the terminal compartment! Danger of electric shock, moving parts (fan) and hot surfaces Risk of injury! WARNING...
  • Page 126: Cleaning Of Cross-Counterflow Heat Exchanger

    Installation and Operating Instructions Central ventilation units AIR1 XVP 3. Carefully remove the profile (see Fig.38). Fig38 4. Disassemble the cross-counterflow heat exchanger (see Fig.39). Fig39 5. Remove the dampers (see Fig.40). Fig40 532 Cleaning of cross-counterflow heat exchanger The cross counterflow heat exchanger must be regularly checked for dirt and dust deposits. The cross counterflow heat exchanger must also be checked for damage every 6 months.
  • Page 127 Installation and Operating Instructions Central ventilation units AIR1 XVP The technical data for the standard filter can be found in the table below: Filter Nominal air Number Filter class Dimensions Recommen- volume flow of filters (LxHxW) (mm) ded final (m³/h) pressure diffe- rential (Pa) AIR1 XVP 850 extr.
  • Page 128: Service And Maintenance Of Fans

    Installation and Operating Instructions Central ventilation units AIR1 XVP Service and maintenance of fans Danger to life due to electric shock! DANGER The unit must be fully isolated from the mains power supply before all maintenance and cleaning work Risk of injury due to electric shock, moving parts (fan) and hot surfaces Cleaning the live unit with water can lead to electric shock Risk of injury due to high unit weight! WARNING...
  • Page 129: Cleaning The Housing

    Installation and Operating Instructions Central ventilation units AIR1 XVP 1. Unlock and open the doors with the key included in the scope of delivery (see Fig.46). Fig46 2. Clean the condensate tray with a cloth ( see Fig.47). Fig47 Cleaning the housing Danger to life due to electric shock! DANGER The unit must be fully isolated from the mains power supply before all maintenance and cleaning work.
  • Page 130: Alarms

    Installation and Operating Instructions Central ventilation units AIR1 XVP • Manual = The heat recovery control output can be manually set for testing between 0 to 100 %. Manual: xxx.x – The value for the control output is set between 0 and 100 % here. e Functions P1 heater (pump warm water auxiliary heater) •...
  • Page 131 Installation and Operating Instructions Central ventilation units AIR1 XVP Alarm Priority Stop Check/Solution Malfunction extract air fan • Please make sure that the volume flow of ventilation stage minimal is not setto low. • Check pressure hose connection (also inside the pressure sensor) •...
  • Page 132 Installation and Operating Instructions Central ventilation units AIR1 XVP Alarm Priority Stop Check/Solution DX Defrosting mode active • Alarm ends automatically once the external unit finishes its defrosting process Frost protection sensor • Check external thermostat • Check wiring Manual mode alarms Output manual operation •...
  • Page 133 Installation and Operating Instructions Central ventilation units AIR1 XVP Alarm Priority Stop Check/Solution Frequency converter alarms Alarm frequency converter SAF • Check motor and wiring Alarm frequency converter EAF • Check motor and wiring Communication error frequency • Supply air fan not receiving Modbus signal •...
  • Page 134: Accessory

    Installation and Operating Instructions Central ventilation units AIR1 XVP 510 Accessory Refer to the respective operating instructions for the accessories. Accessory (AIR1-XVP 850 - 3500) Ref no AIR1-BE TOUCH 2 Controller 40751 AIR1-BE ECO Controller 06186 AIR1-CAP Extension kit for pressure sensor...
  • Page 135 Installation and Operating Instructions Central ventilation units AIR1 XVP Accessory (AIR1-XVP 2500) Ref no ELF-AIR1 XVP 2500/ePM10 50%/48 Outside air pre-filter 40527 ELF-AIR1 XVP 2500/ePM11 80%/96 Outside air filter 40529 AIR1-EVH XVP 2500 Electrical preheater (contactor) 40496 AIR1-ENH XVP 2500 Electrical auxiliary heater (contactor) 40497 AIR1-NH WW XVP 2500...
  • Page 136 Installation and Operating Instructions Central ventilation units AIR1 XVP CHAPTER 6 DECLARATION OF CONFORMITY...
  • Page 137 Installation and Operating Instructions Central ventilation units AIR1 XVP...
  • Page 138 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP FRANÇAIS Sommaire CHAPITRE 1 INFORMATIONS GÉNÉRALES  PAGE 2 Informations importantes ............................ Page 2 Demande de garantie – Réserves du constructeur ..................... Page 2 Règlementations – Normes ..........................Page 2 Domaines d’utilisation –...
  • Page 139 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP CHAPITRE 3 DONNÉES TECHNIQUES  PAGE 38 Performances et données techniques......................Page 38 Vue de l’appareil ............................. Page 39 Dimensions ..............................Page 40 Courbes de performance ..........................Page 41 CHAPITRE 4 DONNÉES TECHNIQUES  PAGE 41 Modes de fonctionnement..........................
  • Page 140: Informations Importantes

    Règlementations – Normes Sous réserve d’une installation correcte et d’une utilisation appropriée, cet appareil est conforme aux directives CE en vigueur au moment de sa fabrication. Les centrales AIR1 XVP.. d’Helios sont conformes à la directive ErP 2018 (directive sur l’écoconception) en vigueur.
  • Page 141: Consignes De Montage Générales

    Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP Ces appareils ne sont pas destinés à être installés dans des locaux accessibles au public. Les restrictions d’utilisation des centrales AIR1 XH sont présentées dans le tableau suivant :: AIR1 XVP AIR1 XVP AIR1 XVP AIR1 XVP...
  • Page 142: Transport

    Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP déshydrateurs et un indicateur d’humidité). Stocker le matériel dans un endroit à l’abri de la pluie, exempt de vibrations et de variations de températures excessives (plage de température ambiante : 0 °C min. / + 40 °C max.). Les dom- mages dus à...
  • Page 143: Foyers De Combustion

    Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP – Introduire la tringle de transport dans les trous du socle. – Fixer solidement la tringle de transport avec les vis. – Placer la chaîne ou le câble à l’extrémité de la tringle de transport. –...
  • Page 144: Montage Mécanique

    Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP – que les consommables usagés sont triés et séparés en fonction de leurs caractéristiques respectives. Le contrôleur de ce produit contient des piles. Conformément à la loi sur les piles (BattG), nous sommes tenus de vous informer de ce qui suit : Les piles et accumulateurs ne doivent pas être jetés avec les ordures ménagères.
  • Page 145: Mise De Niveau De L'appareil

    Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP Il convient de veiller à ce qu’un espace suffisant soit disponible pour les travaux de maintenance Par consé- POINT IMPORTANT quent, les mesures doivent être marquées avant le montage de l’appareil Il est plus facile d’installer les accessoires avant de positionner et de monter définitivement l’appareil puisqu’il est alors REMARQUE possible d’accéder aux deux côtés.
  • Page 146 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP 2. Fixer le support de conduits (voir Fig.7). Fig7 3. Fixer le coude du conduit sous le bac à condensat. S’assurer que la construction est étanche en faisant tourner le raccord (voir Fig.8).
  • Page 147: Raccordement Des Conduits Sur La Centrale

    Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP 6. Dévisser le bouchon de condensat de la vis et serrer la vis à l’aide d’un tournevis (voir Fig.11). Fig11 Raccordement des conduits sur la centrale Les appareils de ventilation AIR1 XVP 850/1200/1800 ont des piquages ronds (Fig.12). Les appareils de ventilation AIR1 XVP 2500/3500 ont des piquages rectangulaires (Fig.13).
  • Page 148: Raccordement Électrique

    Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP 1. Déverrouiller les portes avec la clé fournie et ouvrir les portes (voir Fig.15). Fig15 2. Retirer les vis des glissières du filtre, placer les glissières du filtre vers le haut et les fixer dans les rivets filetés (voir Fig.16).
  • Page 149: Fixation De L'interrupteur Principal

    L’interrupteur principal fait partie de la livraison et est joint à l’emballage (voir chap. 2.1.1 „Réception de la marchandi- se“). Pour les séries AIR1-XVP 850 - 1800, l’interrupteur principal (➊) est monté en haut. Pour les séries AIR1-XVP 2500/3500, l’interrupteur principal (➋) est monté sur le côté, à droite ou à gauche, à l’avant ou à...
  • Page 150: Raccordement Au Réseau Électrique

    Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP 2. Visser l’interrupteur principal avec les vis M4x10 sur les panneaux ou sur le côté du boîtier (voir Fig.20). Fig20 3. Ouvrir le boîtier de l’interrupteur principal (voir Fig.21). Vérifier la section du câble utilisé pour le raccordement élec- trique.
  • Page 151: Raccordement De La Commande À Distance

    Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP 2. Ouvrir le couvercle du coffret électrique (voir Fig.25a). 3. Vérifier la section du câble utilisé pour le raccordement électrique. 4. Introduire le câble d’alimentation dans l’appareil (voir Fig.25b, c). Fig25 ...
  • Page 152: Raccordement Des Sondes De Qualité De L'air

    Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP 4. Connecter l’autre extrémité du câble à la commande à distance (voir schéma de raccordement). Fig29 AIR1 BE-ECO AIR1 BE-TOUCH 2 294 Modbus / Bacnet Les centrales AIR1 XH disposent d’une liaison RS-485 et d’une liaison Ethernet. La liaison RS-485 est utilisée pour la communication interne des sondes de pression.
  • Page 153: Schémas De Raccordement

    Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP 210 Schémas de raccordement AIR1-XVP 850 Schéma de raccorde- ment principal SS-1506...
  • Page 154 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP AIR1-XVP 850 Préchauffage électrique/ Chauffage électrique d‘appoint SS-1516...
  • Page 155 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP AIR1-XVP 1250 Schéma de raccorde- ment principal SS-1507...
  • Page 156 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP AIR1-XVP 1250 Préchauffage électrique/ Chauffage électrique d‘appoint SS-1517...
  • Page 157 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP AIR1-XVP 1250 Préchauffage électrique SS-1518...
  • Page 158 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP AIR1-XVP 1800 Schéma de raccorde- ment principal SS-1508...
  • Page 159 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP AIR1-XVP 1800 Préchauffage électrique/ Chauffage électrique d‘appoint SS-1519...
  • Page 160 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP AIR1-XVP 2500 Schéma de raccorde- ment principal SS-1509...
  • Page 161 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP AIR1-XVP 2500 Préchauffage électrique/ Chauffage électrique d‘appoint SS-1520...
  • Page 162 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP AIR1-XVP 3500 Schéma de raccorde- ment principal SS-1510...
  • Page 163 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP AIR1-XVP 3500 Préchauffage électrique/ Chauffage électrique d‘appoint SS-1521...
  • Page 164: Assistant De Mise En Service (" Wizard ")

    Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP 211 Assistant de mise en service (« wizard ») Les principaux réglages de la centrale peuvent être effectués à l’aide de l’assistant de mise en service (à l’exception Assistant de mise en service du paramétrage, du mode d’urgence, de l’heure / la date et de l’horloge).
  • Page 165: Activation Du Menu De L'assistant De Mise En Service (" Wizard ")

    Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP 2112 Activation du menu de l’assistant de mise en service (« wizard ») Étape 1 : se connecter en tant qu’administrateur (droits d’accès) Régulation du ventilateur ↑ Horloge → Droits d’accès ↓ → Connexion Déconnexion Modification du code Connexion...
  • Page 166: Sélection De L'appareil

    Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP 2114 Sélection de l’appareil Sélection des centrales concernées : → • Appareil de ventilation centrale AIR1-XVP AIR1-XVP Serie Seule une centrale peut être sélectionnée. Le mot « aucun » s’affiche automatiquement dans les deux autres groupes. Le dernier réglage est valable.
  • Page 167 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP b Régulation de l’air soufflé en fonction de la température extérieure La valeur de consigne de la température de l’air soufflé peut être régulée en fonction de la température extérieure afin de mieux compenser les déperditions des pièces.
  • Page 168 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP d Régulation en cascade de la température de l’air extrait La régulation en cascade de la température de l’air extrait et de la température de l’air soufflé est utilisée pour obtenir une température ambiante constante et réglable.
  • Page 169 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP La valeur de consigne de la température ambiante est compensée en fonction de la température extérieure à l’aide d’une courbe de régulation à 8 points. Exemple : Température de l’air La température ambiante extérieur [°C] [°C] - 20...
  • Page 170: Mode De Ventilation

    Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP Valeur de consigne en fonc- ↑ tion de l’air extérieur 10,0 °C = 18,0 °C ↓ 15,0 °C = 18,0 °C 2117 Mode de ventilation Le mode de ventilation est paramétré lors de la mise en service. Par la suite, ces paramètres peuvent uniquement être modifiés dans l’assistant de mise en service (niveau administrateur).
  • Page 171: Préchauffage Électrique

    Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP c Pression constante Possible uniquement avec la sonde de pression AIR1-CAP disponible en tant qu’accessoire. Il peut être installé dans la REMARQUE gaine d’air soufflé ou dans la gaine d’air extrait. Un niveau de ventilation est disponible : •...
  • Page 172: Type De Chauffage

    Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP Appuyer sur la touche pour accéder au menu Type de filtre air extrait. Appuyer sur la touche pour sélectionner le type de filtre pour l’air extrait et confirmer en appuyant sur la touche 21111 Type de chauffage Sélection des types de post chauffages disponibles.
  • Page 173: Ventilation Pilotée Par Sondes (Ventilation À La Demande - Vod)

    Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP Cette fonction est utilisée pour bloquer la fonction de chauffage après la surventilation pendant la période définie. Appuyer sur la touche puis procéder au réglage avec la touche . Confirmer avec la touche Sonde d’air extérieur ↑...
  • Page 174: Achèvement De L'assistant De Mise En Service

    Normal fermé 213 Paramétrage Le paramétrage s’effectue dans le menu principal après l’achèvement de l’assistant de mise en service. Il s’effectue via le sous-menu Régulation du ventilateur. Helios Ventilateurs 2019-XX-XX 09:30 Système : éteint Valeur de consigne : 19,5 Va- leur réelle : 0.0 °C...
  • Page 175 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP En fonction du mode de fonctionnement sélectionné (débit d’air constant, pression constante, vitesse constante), les réglages suivants doivent être effectués : a Débit d’air constant • Régulation du débit d’air du ventilateur de soufflage •...
  • Page 176 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP CHAPITRE 3 Performances et données techniques DONNÉES TECH- Les liaisons mécaniques doivent être réalisées correctement pour atteindre l’efficacité maximale de l’appareil. L’effica- NIQUES cité thermique, le niveau sonore et la puissance électrique de l’appareil peuvent varier en fonction de l’environnement dans lequel il fonctionne.
  • Page 177: Vue De L'appareil

    Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP Vue de l’appareil AIR1 XVP 850-1800 Fig30 AIR1 XVP 2500-3500 Fig31 Interrupteur principal Préfiltre d'air extérieur (ePM10 50% /en option) Air rejeté Filtre d'air extrait (ePM10 50%) Air extérieur Batterie eau chaude/postchauffage électrique (en option) Air extrait Clapet de bypass...
  • Page 178: Dimensions

    Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP Dimensions AIR1-XVP 850- 1800 Fig32 ø32 ODA - Outdoor Air / Außenluft / Air extérieur EHA - Exhaust Air / Fortluft /Air rejeté ETA - Extract Air / Abluft / Air repris SUP - Supply Air / Zuluft / Air soufflé...
  • Page 179: Courbes De Performance

    Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP Courbes de performance AIR1-XVP 850 AIR1-XVP 1250 Δp Δp V · (m³/h) V · (m³/h) 1000 1200 1400 750 1000 1250 1500 1750 2000 AIR1-XVP 1800 AIR1-XVP 2500 Δp Δp...
  • Page 180 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP 411 Commande manuelle Options pour la Commande manuelle : • Réduit • Normal • Boost • éteint (veille) Selon le mode de commande manuelle choisi, la centrale fonctionne avec les valeurs de consigne définies pour le niveau sélectionné.
  • Page 181: Temporisation

    Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP → Heure / Date Minuterie Normal Minuterie Réduit Minuterie Boost → Minuterie VOD Minuterie Mode recyclage Vacances Temporisation Priorités du programme horaire (priorité la plus élevée en premier) : • Minuterie Boost •...
  • Page 182 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP • Réduit : activation du niveau de ventilation Réduit • Boost : activation du niveau de ventilation Boost • Diff : hystérésis Temps d’arrêt VOD : lorsque la centrale fonctionne pendant plus de 2 heures au niveau de ventilation Boost, la venti- lation pilotée par sonde est interrompue pendant le temps d’arrêt défini.
  • Page 183: Fonctions

    Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP Après l’actionnement du contact, la centrale fonctionne alors au niveau de ventilation sélectionné pendant la durée programmée. Il est donc possible d’utiliser les touches. Si la temporisation est réglée sur 0, la centrale fonctionne jusqu’à ce que le contact correspondant ne soit plus actionné. Réglage de la temporisation : •...
  • Page 184: Protection Antigel De La Batterie Eau Chaude

    Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP l’air extérieur est < -4 °C et la température de l’air rejeté < 2 °C • Régulation continue de la puissance du préchauffage jusqu’à ce qu’une température de l’air rejeté de + 4 °C ou 100 % de la puissance soit atteinte.
  • Page 185: Contrôle Des Filtres

    Si le mot de passe administrateur a été modifié puis oublié, un mot de passe maître temporaire peut être demandé au service après-vent d’Helios. Les menus ci-après sont uniquement consultables en lecture seule avec les niveaux utilisateur suivants (ou un niveau utilisateur supérieur)
  • Page 186: Menu Overview Air1-Be Eco

    Notice de montage et d'utilisation Menu principal Appareils de ventilation centrale AIR1 XVP Helios Ventilatoren AIR1 XVP 850 Programm vent. syst. EXOreal C Version Choose Language 2023-06-22 09:30 Cross Counter Flow U Version: 3.7-0-51 3.5-1-04 Choisir la langue Système: Arrêté...
  • Page 187 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP Les sous-menus du menu principal (partie 2 de 2) 7. Entrées / Sorties 9. Réglages AI1: 0.0 Inutilisée Ctrl température Ctrl soufflage AI Ext3 AI2: 45.5 humides Ctrl débit Bande-P: 33.0 °C AI Ext4 AI3: 0.0 Inutilisée...
  • Page 188 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP Les sous-menus du Configuration (partie 1 de 4) Système Communication Recyclage Choose Language Unité d‘extension 1 Activer ctrl temp Consigne constante Fonction port1 Aucune quand recyclage ou décalage consigne Choisir la langue Ext et v.freq/press French...
  • Page 189 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP Les sous-menus du Configuration (partie 2 de 4) Entrées / Sorties Réglages sonde AI1: Pression VAS AI1... AI Ext3 Sign: Inutilisée 0.0V: 0.0 AI Ext4 Valeur mes: NaN 10.0V: 500.0 Pa Compensation: 0.0 Facteur filtre: 0.2 Pression A Ext3...
  • Page 190 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP Les sous-menus du Configuration (partie 3 de 4) Fonction incendie Surventilation Ctrl Pompes Fonction CCF: Surventilation P1-Chaud Arrêt pompe: Oui Inactif active: Oui P1-Échangeur Délai arrêt: 1 Min Opération si alarme: Temp ext activation: P1-Froid T °ext arrêt: 0°C...
  • Page 191 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP Les sous-menus du Configuration (partie 4 de 4) Séquenceur Config alarmes Autres paramètres Séquenceur chauff Séquenceur chauff: Marche étg1: 10 % Alarmes (1-125): 1 1. Défaut VAS Tempo VAS Séquenceur refroid Séquentiel Arrêt étg1: 5 %...
  • Page 192: Entretien Et Maintenance

    Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP CHAPITRE 5 Entretien et maintenance ENTRETIEN ET Il incombe généralement à l’utilisateur de procéder au remplacement des filtres. Les autres travaux de nettoyage et de MAINTENANCE maintenance doivent être effectués exclusivement par un électricien qualifié. Danger de mort par choc électrique ! DANGER Mettre impérativement l’appareil hors tension avant tous travaux d’entretien, d’installation et avant l’ouverture...
  • Page 193 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP Entretien et maintenance de l’échangeur à contre-courant Danger de mort ! Mettre impérativement l’appareil hors tension avant tous travaux d’entretien, d’installation et avant l’ouverture DANGER du boîtier électronique ! Risques de choc électrique, pièces mobiles (ventilateur) et surfaces chaudes Risque de blessure ! AVERTISSEMENT Les échangeurs de chaleur pèsent lourd et peuvent contenir des condensats !
  • Page 194 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP 3. Retirer soigneusement le profilé (voir Fig.38). Fig38 4. Démonter l'échangeur à contre-courant (voir Fig.39). Fig39 5. Retirer les volets (voir Fig.40). Fig40 532 Nettoyage Il convient de contrôler régulièrement l’absence de saletés ou de dépôts de poussière au niveau de l’échangeur à contre-courant.
  • Page 195 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP Les données techniques des filtres standards sont indiquées dans le tableau suivant : Filtres Débit d’air Nombre Classe de filtre Dimensions Différence nominal (L x h x l) (mm) de pression (m3/h) filtres finale recom- mandée (Pa) Filtre d’air extrait AIR1 XVP 850 ePM10 50 %...
  • Page 196: Nettoyage Du Bac À Condensat

    Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP Vérifier l’absence de saleté, d’endommagement et de corrosion sur le ventilateur tous les 6 mois : – une inspection régulière et un nettoyage périodique sont nécessaires afin d’éviter tout déséquilibre lié à la saleté. –...
  • Page 197: Nettoyage Du Caisson

    Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP 2. Nettoyer le bac à condensat avec un chiffon ( voir Fig.47). Fig47 Nettoyage du caisson Danger de mort par choc électrique ! DANGER Mettre impérativement l’appareil hors tension avant tous travaux d’entretien et de nettoyage. Risque de blessure par choc électrique, pièces mobiles (ventilateur) et surfaces chaudes –...
  • Page 198: Alarmes

    Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP • Éteint = la pompe est éteinte. • Auto = la pompe est allumée et éteinte automatiquement par le régulateur comme lors du fonctionnement normal de la centrale. • Allumé = la pompe est allumée. h Fonctions du registre d’air extérieur •...
  • Page 199 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP Alarme Priorité Arrêt Vérification / Solution Changement de filtre Alarme filtre 1 • Remplacer le filtre d’air rejeté Alarme filtre 2 • Remplacer le filtre d’air soufflé Alarmes de température Erreur régul.
  • Page 200 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP Alarme Priorité Arrêt Vérification / Solution Vas à frég. var. en mode manuel • Pilotage via le mode de commande manuelle Var en mode manuel • Pilotage via le mode de commande manuelle Var à...
  • Page 201 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP Alarme Priorité Arrêt Vérification / Solution Erreur de communication unités d’extension Erreur com. unité d'extension 3 • Communication interrompue avec la sonde de pression du ventilateur de soufflage • Vérifier le câblage Modbus entre la sonde de pression et le dispositif de commande Erreur com.
  • Page 202 Type de sonde : Consigne de pression : Seuils : Préchauffage : ACTIF / INACTIF 510 Accessoire Pour les accessoires, voir les notices d’utilisation respectives. Accessoire (AIR1-XVP 850 - 3500) Ref no AIR1-BE TOUCH 2 Commande à distance 40751 AIR1-BE ECO Commande à...
  • Page 203 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP Accessoire (AIR1-XVP 1250) Ref no ELF-AIR1 XVP 1250/ePM10 50%/48 Préfiltre d'air extérieur 40519 ELF-AIR1 XVP 1250/ePM11 80%/96 Filtre d'air extérieur 40521 Préchauffage électrique 40480 AIR1-EVH XVP 1250-3,6 (protection) AIR1-EVH XVP 1250-2,6 Préchauffage électrique 40481 (protection)
  • Page 204: Démontage Et Recyclage

    Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP 512 Démontage et recyclage Danger de mort par choc électrique ! DANGER Un choc électrique peut causer la mort ou de graves blessures – S’assurer que l’appareil est hors tension et isolé. Mettre l’appareil à la terre, le court-circuiter et protéger les compo- sants adjacents sous tension.
  • Page 205 EU Declaration of Conformity to EC Machinery Directive 2006/42/EC Annex II Part 1A / Déclaration de conformité UE selon la Directive CE relative aux machines 2006/42 Note II Partie 1A Helios Ventilatoren GmbH + Co KG Lupfenstr. 8, D-78056 Villingen-Schwenningen Hiermit erklären wir, dass die Produkte in Übereinstimmung mit den untenstehenden Richtlinien entwickelt,...
  • Page 206 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP...
  • Page 207 Notice de montage et d'utilisation Appareils de ventilation centrale AIR1 XVP...
  • Page 208 HELIOS Ventilatoren GmbH + Co KG · Lupfenstraße 8 · 78056 VS-Schwenningen HELIOS Ventilateurs · Le Carré des Aviateurs · 157 avenue Charles Floquet · 93155 Le Blanc Mesnil Cedex CH HELIOS Ventilatoren AG · Tannstrasse 4 · 8112 Otelfingen GB HELIOS Ventilation Systems Ltd.

This manual is also suitable for:

Air1-xvp 3500Air1 xvp 2500Air1 xvp 1250Air1 xvp 1800