5.3 ERROR CODES AND TROUBLESHOOTING

Error Code
Explanation
CH Temperature
H1
Sensor Error
DHW
H2
Temperature
Sensor Error
CH Circuit Low
H3
Water Pressure
Error
Safety Thermostat
Error
H4
Boiler temp >=95°C
Limit Thermostat
H5
Error
Boiler temp >=93°C
Main Heat
H6
Exchanger Water
Level Error
CH Circuit High
H7
Water Pressure
Error
Ambient
H8
Temperature
Probe Error
 These solutions can only be performed by AUTHORIZED SERVICE PERSONNEL.
 These solution steps can be performed by end users.
Reason
• Disconnected sensor cable
• NTC sensor failure
• Mainboard failure
• Disconnected sensor cable
• NTC sensor failure
• Mainboard failure
• Aİr trapped in the system
• Water leakage from boiler
or installation
• Expansion tank failure
• Air trapped inside the system
• Valves on the installation
may be closed
• Thermostat failure
• Particule filters may be
clogged.
• Circulation pump failure
• Mainboard failure
• Air trapped inside the system
• Valves on the installation
may be closed
• Thermostat failure
• Particule filters may be
clogged.
• Circulation pump failure
• Mainboard failure
• Air trapped in main heat
exchanger
• Float water level sensor
failure
• Filling valve malfunction
• Expansion tank failure
• Plate heat exchanger
failure
• Return manifold failure
• Disconnected or
damaged probe cable
• Temperature probe
malfunction
40
Solution
 Check the cable and socket
 Replace the NTC sensor
 Replace the mainboard
 Check the cable and socket
 Replace the NTC sensor
 Replace the mainboard
 Vent the air from boiler and radiators then fill
system upto 1.5 bars.
 Check all piping and connections for leakage
 Check the counter pressure of the
expansion tank. Pressurize the tank upto
1.1 bars with nitrogen. If membrane is
damaged replace the tank.
 Vent the air from boiler and radiators then fill
system upto 1.5 bars.
 Make sure all the valves are open
 Check the thermostat connections, replace
thermostat if necessary.
 Clean the filters.
 Turn the rotor manually, check pump electric
connection, replace pump if needed.
 Replace the mainboard.
 Vent the air from boiler and radiators then fill
system upto 1.5 bars.
 Make sure all the valves are open
 Check the thermostat connections, replace
thermostat if necessary.
 Clean the filters.
 Turn the rotor manually, check pump electric
connection, replace pump if needed.
 Replace the mainboard.
 Vent the air inside the mani heat exchanger
using the manual air vent. Fill the system upto
1.5 bar.
 Check the cable of folat water level sensor
 Check if the folater is stuck, clean the part so
the floater moves freely. Replace the float
water level sensor if neccessary.
 Drain the excess water prom the drain valve
on the installation to reduce pressure.
 Check if the filling valve tightly closed.
 Replace the filling valve if its leaking.
 Check the counter pressure of the expansion
tank. Pressurize the tank upto 1.1 bars with
nitrogen. If membrane is damaged replace the
tank.
 Replace the palte heat exchanger.
 Replace the return manifold.
 Check the cable and connection.
 Replace the ambient temperature probe.