6
PARAMETER SETTING

6.2 Parameter Setting Items

Table6.1 lists the parameter setting items.
Setting item
Set the number of modules installed with a single safety CPU module.
No. of boards in
Default value: No setting
module
Setting range: 1 to 2
Enter the head I/O number.
Start I/O No.
Default value: No setting
Setting range: 0000 to 03E0
Set the output data status of the remote output (RY) for the case of the safety CPU module stop.
Fixed to forced clear if the safety CPU module is in SAFETY MODE.
Case of safety CPU
Default value: Refresh
STOP setting
Setting range: Refresh
Set the station number of a remote station for which the line test is performed. Setting is
available only when the mode is set to "Line test".
Station No.
Default value: 0 (All stations)
Setting range: 0 to 64
Set the operation mode.(*)
For communication with slave stations, select "Safety remote net (Ver.1 mode)". For operation
check, select "Hardware test" or "Line test". To disable communication, select "Off line".
Default value: Safety remote net (Ver.1 mode)
Mode
Setting range: Safety remote net (Ver.1 mode)
Set the transmission speed of the module.
Default value: 156kbps
Setting range: 156kbps
Transmission speed
Set the monitoring time used between the safety master station and safety remote stations.
Safety refresh
Default value: 200 (ms)
monitoring time
Setting range: 1 to 65535 (ms)
Set the monitoring time used in a safety remote station.
Safety data
Default value: 400 (ms)
monitoring time
Setting range: 1 to 65535 (ms)
Set a link ID for each safety master module.
Default value: 0
Link ID
Setting range: 0 to 7
Set the number of safety remote I/O stations, standard remote I/O stations and remote device
stations that are connected to the safety master station. (including reserved stations)
All connect count
Default value: 64
Setting range: 1 to 64
* When "Offline" is set, it does not communicate with remote stations as a safety master station.
"CC-LINK PARAMETER ERROR" occurs if "Hardware test" or "Line test" is set when the safety CPU module is in any other than TEST
MODE.
6
- 2
6.2 Parameter Setting Items
Table6.1 Parameter setting items (1/2)
Description
Clears compulsorily
Off line
Hardware test
Line test
625kbps
2.5Mbps
5Mbps
10Mbps
Reference
section
Section 6.3.1
(2)(a)
Section 6.3.1
(2)(b)
Section 4.2.10,
Section 6.3.1
(2)(d)
Section 6.3.1
(2)(e)
Section 6.3.1
(2)(f)
Section 4.2.6,
Section 5.2.1,
Section 6.3.1
(2)(g)
Section 4.2.14,
Section 5.2.1,
Section 6.3.1
(2)(h)
Section 6.3.1
(2)(i)
Section 6.3.1
(2)(j)