Mitsubishi Electric MELSEC QS Series User Manual page 126

Cc-link safety system master module
Hide thumbs Also See for MELSEC QS Series:
Table of Contents

Advertisement

8
PROGRAMMING SPECIFICATIONS
Number
Name
SW0080
(680
)
H
SW0081
(681
)
H
Other station
data link
status
*4 *5
SW0082
(682
)
H
SW0083
(683
)
H
SW0084
(684
)
H
SW0085
Other station
(685
)
watchdog
H
timer error
occurrence
SW0086
*4
status
(686
)
H
SW0087
(687
)
H
SW0088
(688
)
H
SW0089
(689
)
Other station
H
fuse blown
SW008A
*4
status
(68A
)
H
SW008B
(68B
)
H
* 1 Safety remote net (Ver. 1 mode)
* 2 Off line, Hardware test or Line test.
* 4 Bits for the number of occupied stations are turned on.
* 5 It takes up to 6 seconds from when a slave station error is identified in the safety master station until the Other station data link
status (SW0080 to SW0083) turns on.
The time spent to turn it ON varies depending on the system configuration and the faulty status.
8
- 23
8.3 Link Special Relays and Registers (SB/SW)
8.3.2 Link special registers (SW)
Table8.6 Link Special Register List (4/7)
Description
Stores the data link status of each station. Reserved stations are
excluded.
0 : Normal
1 : Data link error occurred
b15
b14
b13
SW0080
16
15
14
SW0081
32
31
30
SW0082
48
47
46
SW0083
64
63
62
Numbers 1 to 64 in the above table indicate the station numbers.
Indicates the watchdog timer error status. Reserved stations are
excluded.
0 : No watchdog timer error
1 : Watchdog timer error occurred
b15
b14
b13
SW0084
16
15
14
SW0085
32
31
30
SW0086
48
47
46
SW0087
64
63
62
Numbers 1 to 64 in the above table indicate the station numbers.
Stores the fuse blown status of each station. Reserved stations are
excluded.
0 : Normal
1 : Abnormal
b15
b14
b13
SW0088
16
15
14
SW0089
32
31
30
SW008A
48
47
46
SW008B
64
63
62
Numbers 1 to 64 in the above table indicate the station numbers.
to
b12
b3
b2
b1
13
to
4
3
2
to
29
20
19
18
to
45
36
35
34
61
to
52
51
50
to
b12
b3
b2
b1
to
13
4
3
2
29
20
19
18
to
to
45
36
35
34
61
52
51
50
to
b12
b3
b2
b1
to
13
4
3
2
to
20
19
18
29
to
45
36
35
34
to
52
51
61
to
50
Availability
(
:Available,
:Not available)
1
Online*
SAFETY
TEST
MODE
MODE
b0
1
17
33
49
b0
1
17
33
49
b0
1
17
33
49
2
Offline*

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec-qs0j61bt12

Table of Contents