6
PARAMETER SETTING
Setting item
Set a device to which remote input (RX) is refreshed by the automatic refresh function.
Default value: No setting
Remote input (RX)
Setting range: X, M, B, D, W (The device number must be within the device range of the
Set a device to which remote output (RY) is refreshed by the automatic refresh function.
Default value: No setting
Remote output (RY)
Setting range: Y, M, B, D, W, T, ST, C (The device number must be within the device range of
Set a device to which remote register (RWr) is refreshed by the automatic refresh function.
Remote register
Default value: No setting
(RWr)
Setting range: W, D, B, M (The device number must be within the device range of the safety
Set a device to which remote register (RWw) is refreshed by the automatic refresh function.
Remote register
Default value: No setting
(RWw)
Setting range: W, D, B, M, T, ST, C (The device number must be within the device range of
Set a device to which link special relay (SB) is refreshed by the automatic refresh function.
Default value: No setting
Special relay (SB)
Setting range: SB, B, M, W, D (The device number must be within the device range of the
Set a device to which link special register (SW) is refreshed by the automatic refresh function.
Special register
Default value: No setting
(SW)
Setting range: SW, W, D, B, M (The device number must be within the device range of the
Set the number of retries for the case where a communication error occurs.
Retry count
Default value: 3 (times)
Setting range: 1 to 7 (times)
Set the number of safety remote I/O stations, standard remote I/O stations and remote device
Automatic
stations that can rejoin the network in one link scan.
reconnection station
Default value: 1
count
Setting range: 1 to 10
Specify whether to make the link scan synchronous or asynchronous with the sequence scan.
Scan mode setting
Default value: Synchronous
Setting range: Synchronous or Asynchronous
Set the type of a connected safety remote I/O station, standard remote I/O station or remote
device station.
Default value:
Station information
setting
Setting range
Station type:
Number of occupied stations: 1 to 4
Station No.:
Reserved station setting:
Safety station
Set a product model name, production information, etc. of a safety remote I/O station.
information
Safety remote
Set parameters of safety remote stations.
station setting
For setting details, refer to manual of the safety remote station to be used.
Table6.1 Parameter setting items (2/2)
Description
safety CPU module.)
the safety CPU module.)
CPU module.)
the safety CPU module.)
safety CPU module.)
safety CPU module.)
"Standard remote I/O station, 1 station occupied, station No. 1,
no reserved station" to "Standard remote I/O station, 1 station
occupied, station No. 64, no reserved station"
Safety remote I/O station, standard remote I/O station, remote
device station
1 to 64
Not specified, Specified
6.2 Parameter Setting Items
1
Reference
section
Section 6.3.1
(2)(k)
2
Section 6.3.1
(2)(l)
Section 6.3.1
3
(2)(m)
Section 6.3.1
(2)(n)
4
Section 6.3.1
(2)(o)
Section 6.3.1
(2)(p)
5
Section 6.3.1
(2)(q)
Section 4.2.7,
Section 6.3.1
(2)(r)
Section 4.2.1 to
6
Section 4.2.2,
Section 6.3.1
(2)(s)
Section 6.3.1
7
(2)(t)
Section 6.3.1
8
(2)(u)
6
- 3