Number Of Pt100 Temperature Sensors Used - Pepperl+Fuchs Bebco EPS 5500 Series User Manual

Type z and ex pzc purge and pressurization system
Table of Contents

Advertisement

4.7. Number of PT100 Temperature Sensors Used

The 5500 control unit allows up to two 2-wire PT100s to be connected to the unit for
monitoring and controlling temperatures in the pressurized enclosure.
Each sensor can be located up to 3 m from the control unit input. Using two PT100s
allows various placements within the enclosure to capture the variation of heat in
locations where electronic devices are located.
In order for the temperature inputs to work, Number of PT100s and Temperature
enabled must be activated. An incorrect number of PT100s selected will give a error on
the PT100 input, the PT100 LED will light up, and TEMP AL will be activated if selected
for K2.