Program 2 - Pepperl+Fuchs Bebco EPS 5500 Series User Manual

Type z and ex pzc purge and pressurization system
Table of Contents

Advertisement

5500 S
M
 P
erieS
anual
4.4.2

Program 2

Program 2 is used in hazardous gas atmospheres.
Sequence of Events for Program 2
P < P4
Purge
valve
ON
P > P1
Pre-Purge
The purge valve (SV) is energized when enclosure pressure is greater than P1.
z
If enclosure pressure goes above P4 during purging, the SV shuts off but will energize when
z
below P4. Oscillation of SV may be noticed.
Setting the pressurization valve on the manifold has to be done after purging, or the power to SV
z
will have to be interrupted to set this pressure. The solenoid valve is energized once enclosure
pressure is above P1. Adjusting the pressurization valve before the solenoid valve is energized
will allow the enclosure pressure to be above P1 when purging is completed. Fine adjustment of
P1 can be achieved after purging when the solenoid valve is off.
The purge timer begins counting down when enclosure pressure is greater than P3 and must
z
remain greater than P3 to purge successfully. If the pressure drops below P3 at any time, or for
any length of time during purging, the purge timer is reset and will not begin counting down until
pressure is greater than P3.
Operation Mode
After the purge timer counts down, the SV shuts off and K1 is energized.
z
If enclosure pressure drops below P2, the SV is energized and will stay energized for the value of
z
HYST (%, leakage compensation). If HYST is set to 0, leakage compensation is turned off.
If enclosure pressure drops below P1, K1 remains on and an alarm shall be implemented. K2 can
z
be set to P- or Alarm to indicate below safe or operating pressure.
If enclosure pressure goes above P4, K1 remains. If K2 is set up as Alarm, K2 will energize.
z
WARNINg!
If enclosure pressure is below P1 when K1 is used to provide power to the
enclosure during operation, K1 will remain energized. An alarm is required and
must be located such that an operator will be notified of the alarm.
46
rograMMing
Start
P > P3
timer
HYST > 0
P < P2
K1 ON
t=0
P > P2
Bypass
ON
In menu
Purge valve
ON
K1 ON
P < P1
K2 ON