Pressure Settings; Minimum Enclosure Pressure "P1; Alarm Pressure "P2 - Pepperl+Fuchs Bebco EPS 5500 Series User Manual

Type z and ex pzc purge and pressurization system
Table of Contents

Advertisement

5500 S
M
 P
erieS
anual
The number of volume exchange depends on
the item being purged and

the standard it is being evaluated to.

Number of exchanges
4
5
10 (motors)
EXAMPLE
P3=
Vent=
Enclosure volume=
Flow rate from P3
(see table)
NEC (Class/Division)
Zone (ATEX, IECEx)
NFPA:
Zone:
Motors:
4.5.2

Pressure Settings

4.5.2.1 Minimum Enclosure Pressure "P1"

In accordance with the applicable standards and tolerances on the 5500 pressure sensor, the minimum
operating pressures are as follows:
Gas environments: 0.7 mbar (0.25 in wc)

Dust environments: 1.6 mbar (0.65 in wc)

When enclosure pressure drops below P1 during operation mode, the power has to be interrupted. If not,
an alarm has to be generated to address the problem.

4.5.2.2 Alarm Pressure "P2"

If enclosure pressure drops below P2 during operation mode, the solenoid valve will energize until
pressure goes above P2+HYST. Therefore, leakage compensation has to be implemented.
If leakage compensation is not used, the P2 can sound an alarm to indicate that pressure is dropping.
P2 can be adjusted to above P1 and below P3 values.
52
rograMMing
Class/Division (NFPA 496)
X
n/a
X
Class/Division (NFPA 496)
2.6 inches water
EPV-5500-...-02
table for P3: EPV-5500-...-02,
see Section 2.4.2.
10 ft³
11.3 scfm
4 volume exchange
5 volume exchange
4 x 10 ft³ / 11.3 scfm = 3.6 min
5 x 10 ft³ / 11.3 scfm = 4.5 min
10 x 10 ft³ / 11.3 scfm = 8.9 min
Zone (60079-2)
n/a
X
X
Zone (60079-2)
6.5 mbar
282 liters
320 liters/min
4 volume exchange
5 volume exchange
4 x 282 liters / 320 l/min = 3.6 min
5 x 282 liters / 320 l/min = 4.5 min
10 x 282 liters / 320 l/min = 8.9 min

Advertisement

Table of Contents
loading

Table of Contents