Program 3 is used in hazardous gas atmospheres.
Sequence of Events for Program 3
P < P4
Purge
valve
ON
P > P1
Pre-Purge
The purge valve (SV) is energized when enclosure pressure is greater than P1.
z
If enclosure pressure goes above P4 during purging, the SV will shut off but will energize when
z
below P4. Oscillation of SV may be noticed.
Setting the pressurization valve on the manifold must be done after purging, or the power to SV
z
will have to be interrupted to set this pressure. The solenoid valve is energized once enclosure
pressure is above P1. Adjusting the pressurization valve before the solenoid valve is energized
allows the enclosure pressure to be above P1 when purging is completed. Fine adjustment of P1
can be achieved after purging, when the solenoid valve is off.
The purge timer begins counting down when enclosure pressure is greater than P3, and it has to
z
remain greater than P3 to purge successfully. If the pressure drops below P3 at any time, or for
any length of time during purging, the purge timer is reset and will not begin counting down until
pressure is greater than P3.
Operation Mode
After the purge timer counts down, the SV shuts off and K1 is energized.
z
If enclosure pressure drops below P2, the SV is energized and will stay energized for the value of
z
HYST (%, leakage compensation). If HYST is set to 0, leakage compensation is turned off.
If enclosure pressure drops below P1, K1 turns off immediately or after the Shutdown delay timer
z
times out. K1 remains off until the enclosure goes through a successful purging.
If enclosure pressure goes above P4, K1 remains. If K2 is set up as Alarm, K2 will energize.
z
Start
P > P3
timer
t=0
5500 S
erieS
HYST > 0
Purge valve
P < P2
ON
K1 ON
P > P1
Bypass
ON
In menu
M
 P
anual
rograMMing
K1
P < P1
OFF