8.4

Start automatic mode

8.5

During operation

Installation and operating instructions • Wilo-Control EC/ECe-Booster • Ed.02/2023-08
- Pump 2: P2 Hand
- Pump 3: P3 Hand
3.
Start test run: Press the operating button. Pump runs for the set time (Menu 3.10) and
then switches off again.
4.
Check direction of rotation.
Incorrect direction of rotation: Exchange two phases on the pump connection.
Direction of rotation checked and corrected as necessary. The initial configuration is
complete.
Automatic mode after initial configuration
The switchgear is closed.
Configuration complete.
Direction of rotation correct.
Motor current monitoring set correctly.
1.
Start Easy Actions menu: Turn the operating button 180°.
2.
Select the pump for automatic mode: Turn the operating button until the menu item is
displayed:
- Pump 1: P1 Auto
- Pump 2: P2 Auto
- Pump 3: P3 Auto
3.
Press the operating button.
Automatic mode is set for the selected pump. Alternatively, setting can be per-
formed in Menu 3.02 to 3.04.
Automatic mode switched on.
Automatic mode after shutdown
The switchgear is closed.
Checked configuration.
Parameter input enabled: Menu 7.01 shows on.
1.
Press the operating button for 3 s.
Menu 1.00 appears.
2.
Turn the operating button until menu 3.00 appears
3.
Press the operating button.
Menu 3.01 appears.
4.
Press the operating button.
5.
Change value to "on".
6.
Press the operating button.
Value saved, pump enabled.
Automatic mode switched on.
Make sure the following points are observed during operation:
Keep the switchgear closed and secure it against unauthorised opening.
Switchgear attached in an overflow-proof manner (protection class IP54).
Not exposed to direct sunlight.
Ambient temperature: 0 ... 40 °C.
The following items of information are shown on the main screen:
Pump status:
Number of registered pumps
Pump activated/deactivated
Pump On/Off
Operation with standby pump
Control mode
Actual pressure value
Active field bus operation
Furthermore, the following information is available via menu 4: