8.4
Start automatic mode
8.5
During operation
Installation and operating instructions • Wilo-Control EC/ECe-Booster • Ed.02/2023-08
- Pump 2: P2 Hand
- Pump 3: P3 Hand
3.
Start test run: Press the operating button. Pump runs for the set time (Menu 3.10) and
then switches off again.
4.
Check direction of rotation.
⇒
Incorrect direction of rotation: Exchange two phases on the pump connection.
▶
Direction of rotation checked and corrected as necessary. The initial configuration is
complete.
Automatic mode after initial configuration
✓
The switchgear is closed.
✓
Configuration complete.
✓
Direction of rotation correct.
✓
Motor current monitoring set correctly.
1.
Start Easy Actions menu: Turn the operating button 180°.
2.
Select the pump for automatic mode: Turn the operating button until the menu item is
displayed:
- Pump 1: P1 Auto
- Pump 2: P2 Auto
- Pump 3: P3 Auto
3.
Press the operating button.
⇒
Automatic mode is set for the selected pump. Alternatively, setting can be per-
formed in Menu 3.02 to 3.04.
▶
Automatic mode switched on.
Automatic mode after shutdown
✓
The switchgear is closed.
✓
Checked configuration.
✓
Parameter input enabled: Menu 7.01 shows on.
1.
Press the operating button for 3 s.
⇒
Menu 1.00 appears.
2.
Turn the operating button until menu 3.00 appears
3.
Press the operating button.
⇒
Menu 3.01 appears.
4.
Press the operating button.
5.
Change value to "on".
6.
Press the operating button.
⇒
Value saved, pump enabled.
▶
Automatic mode switched on.
Make sure the following points are observed during operation:
•
Keep the switchgear closed and secure it against unauthorised opening.
•
Switchgear attached in an overflow-proof manner (protection class IP54).
•
Not exposed to direct sunlight.
•
Ambient temperature: 0 ... 40 °C.
The following items of information are shown on the main screen:
•
Pump status:
–
Number of registered pumps
–
Pump activated/deactivated
–
Pump On/Off
•
Operation with standby pump
•
Control mode
•
Actual pressure value
•
Active field bus operation
Furthermore, the following information is available via menu 4: