Installation and operating instructions • Wilo-Control EC/ECe-Booster • Ed.02/2023-08
Menu no.
5.41
Description
Allows "pump kick" when status is Extern OFF
Value range
off, on
Factory setting
on
Explanation
Select whether a pump kick may take place or not if the Extern
OFF input is active:
Menu no.
5.42
Description
"Pump kick interval"
Value range
1 ... 336 h
Factory setting
24 h
Explanation
Time after which a pump kick takes place.
Menu no.
5.43
Description
"Pump kick duration"
Value range
0 ... 60 s
Factory setting
5 s
Explanation
How long a pump kick runs for a pump.
Menu no.
5.45
Description
Behaviour during sensor fault – number of pumps to be
switched on
Value range
0 to 3*
Factory setting
0
Explanation
* Maximum value dependent on number of pumps set (Menu
5.02).
Menu no.
5.46
Description
Minimum speed of the pumps
Value range
0 to 50%
Factory setting
30%
Menu no.
5.47
Description
Maximum pump speed
Value range
80 to 100%
Factory setting
100%
off = pump kick deactivated if Extern OFF is active.
on = pump kick activated if Extern OFF is active.