7.2
Menu control
Fig. 33: Operating button function
7.3
Menu type: Main menu or Easy Ac-
tions menu
7.4
Call up the menu
7.5
Quick access to "Easy Actions"
Installation and operating instructions • Wilo-Control EC/ECe-Booster • Ed.02/2023-08
Minimum pressure monitoring
The minimum pressure monitoring is deactivated at the factory (Menu 5.18, factory setting:
0 bar). As soon as a pump is running, the minimum pressure monitoring is active. NO-
TICE! To deactivate the minimum pressure monitoring, set the value in Menu 5.18 to
"0 bar".
An alarm is triggered under the following conditions:
•
The system pressure falls below the underpressure detection threshold (Menu 5.18,
factory setting: 0 bar).
•
The delay time for overpressure and underpressure detection has expired (Menu 5.74,
factory setting: 5 s).
With underpressure monitoring, the system reaction can be set (Menu 5.73):
•
The system continues to operate normally (factory setting). The error code is shown in
the LCD display. The alarm is automatically acknowledged with a short delay when the
pressure threshold is exceeded.
•
The system triggers an alarm and all pumps are switched off. The error code is shown on
the LCD display and the red LED lights up. The output for the collective fault signal (SSM)
is activated. The alarm must be acknowledged manually.
The menu is controlled via the operating button:
•
Turn: Menu selection or settings values.
•
Press: Change menu level, confirm error number or value.
There are two different menus.
•
Main menu: Access to all settings for a complete configuration.
•
Easy Actions menu: Quick access to certain functions.
Observe the following points when using the Easy Actions menu:
–
The Easy Actions menu only offers access to the selected functions. It is not possible
to perform a complete configuration with this.
–
Perform an initial configuration to use the Easy Actions menu.
–
The Easy Actions menu is enabled at the factory. Note, the Easy Actions menu can be
disabled in menu 7.06.
Call up the main menu
1.
Press operating button for 3 seconds.
▶
Menu item 1.00 appears.
Call up the Easy Actions menu
1.
Turn operating button 180°.
⇒
The "Resetting error messages" or "Manual operation pump 1" function appears
2.
Turn operating button an additional 180°.
▶
The other functions are shown. The main screen appears at the end.
The following functions can be called up using the Easy Actions menu:
Reset the current error message
NOTICE! Menu point is only shown when an error is present!
Manual operation pump 1
If the operating button is pressed, pump 1 runs.
If the operating button is released, the pump switches off. The last set
operating mode is active again.
Manual operation pump 2
If the operating button is pressed, pump 2 runs.
If the operating button is released, the pump switches off. The last set
operating mode is active again.