8.3.3
Menu 5: Basic settings
Fig. 36: Menu 5.01
Fig. 37: Menu 5.02
Fig. 38: Menu 5.03
Fig. 39: Menu 5.11
Fig. 40: Menu 5.14
Fig. 41: Menu 5.15
Installation and operating instructions • Wilo-Control EC/ECe-Booster • Ed.02/2023-08
Menu no.
5.01
Description
Control mode
Value range
P-c
Factory setting
Constant pressure control (p-c)
Menu no.
5.02
Description
Number of connected pumps
Value range
1 ... 3
Factory setting
3
Menu no.
5.03
Description
Standby pump
Value range
on, off
Factory setting
off
Explanation
One pump can be used as a standby pump. This pump is not
activated during normal operation. The standby pump is only
activated in the event of pump failure due to a fault. The
standby pump is subject to standstill monitoring. The standby
pump is therefore activated during pump cycling and pump
kick.
•
•
Menu no.
5.11
Description
Pressure sensor measurement range
Value range
1 to 25 bar
Factory setting
16 bar
Menu no.
5.14
Description
PID controller: Proportional factor
Value range
0.1 to 100
Factory setting
5.0
Menu no.
5.15
Description
PID controller: Integral factor
Value range
0 to 300
Factory setting
2.0
on = Standby pump activated
off = Standby pump deactivated