4.2.2.4 Humidifier Water Inlet Pipe

The humidifier water inlet pipe can be connected using a hose or a rigid pipe.
Figure 4-23 Connecting a water inlet pipe
(1) Internal thread connector:
G 1/2 inch; internal thread
connector delivered with the
water inlet pipe of the smart
cooling product
(4) Pagoda connector: G 1/2
inch; connected to a pagoda
connector with outer screw
threads
(7) External thread connector:
G 3/4 inch, reserved for the
smart cooling product
humidifier
(10) Elbow: made of PP-R or
other materials

4.2.2.5 Drainpipe

The drainpipe can be connected using a hose or a rigid pipe.
Issue 13 (2023-08-20)
NO TE
The hose clamp (part 5) is configured by default. Other components need to be purchased.
Copyright © Huawei Digital Power Technologies Co., Ltd.
(2) Rigid pipe conversion
adapter: G 1/2 inch; connected
to a rigid pipe with external
threads
(5) Hose clamp
(8) Active connector: G 3/4
inch, inner thread PP-R
(11) Rigid pipe: made of PP-R
or other materials
4 Installation
(3) Rigid pipe: made of PP-R or
other materials
(6) Hose: made of EPDM or
other materials
(9) Rigid pipe: made of PP-R or
other materials
67