NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
4.9.8.3.3 CAN Teamwork + FE Monitoring
Step 1 Connect teamwork and monitoring communications cables.
Networking
Protocol
Description
Figure 4-95 Connecting communications cables
----End
4.9.8.3.4 CAN Teamwork + RS485 Monitoring
Step 1 Connect teamwork and monitoring communications cables.
Networking
Protocol
Issue 13 (2023-08-20)
CAN Teamwork
CAN
One teamwork network
supports a maximum of 32
units. On the Teamwork
Settings screen of the display
modules of the first and last
units, set Enable teamwork
CAN resistor to Yes.
NO TE
If the Modbus-TCP/SNMP protocol is used, customers can purchase the NetEco (a LAN
switch is required) or a third-party NMS as the monitoring system.
CAN Teamwork
CAN
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 Installation
FE Monitoring
Modbus-TCP/SNMP
-
RS485 Monitoring
Modbus-RTU
128