NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
●
●
Figure 4-20 Operation area requirements for water-cooled modules (unit: mm)
4.2 Installation Preparations
To ensure the optimal operating condition and longest service life, install the
device correctly as required.
4.2.1 Tools
The onsite technical personnel can select tools based on the site requirements.
Issue 13 (2023-08-20)
NO TE
A water strainer with 20 meshes and pressure resistance of 1.6 MPa or higher is
recommended onsite. Pressure resistance of the water strainer is determined by site
requirements. The water strainer should be installed on the external water inlet pipe
and close to the smart cooling product.
The water-cooled module should be installed on a concrete base. The base
requirements are as follows.
Figure 4-19 Concrete base dimensions (unit: mm)
(1) Mounting hole: 4 x M12
The following figure shows the operation area requirements for water-cooled
modules.