NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual

6.5.2 (Optional) Setting Teamwork Parameters

Prerequisites
The teamwork group number and addresses for the smart cooling products have
been set as follows:
Context
The parameters in this section are for reference only. Set practical parameter
values as required.
Procedure
Step 1 On the home screen, tap
Settings screen, as shown in
Figure 6-11 Teamwork Settings
Step 2 Set teamwork parameters.
All teamwork parameters can be set on the master smart cooling product. Only
Teamwork group No., System address, Enable teamwork CAN resistor,
Teamwork function and Networking mode can be set on slave smart cooling
products. Other parameters of the slave units will be modified by the master unit
synchronously.
Parameter
Teamwork group num
System address
Issue 13 (2023-08-20)
Teamwork group No.: Group the smart cooling products in same aisle or
adjacent areas as one, that is, assign one teamwork group number for them.
At most four teamwork groups can be assigned (1–4).
System address: The address (configurable range: 1-32) of each smart cooling
product in the same group must be unique. The smart cooling product with
the smallest unit address is the master unit, which collects, processes, and
delivers group data.
Copyright © Huawei Digital Power Technologies Co., Ltd.
> Teamwork Settings to enter the Teamwork
Figure
6-11.
Description
Specifies the planned teamwork group number. This
parameter should be the same for all units in the same
teamwork group.
Specifies the planned unit address. The addresses of
units in the same teamwork group must be unique.
6 Power-On Commissioning
157