Welding Indoor Unit Pipes - Huawei NetCol5000-A050 User Manual

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A050:
Table of Contents

Advertisement

NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual

4.8.2 Welding Indoor Unit Pipes

Precautions
Table 4-13 Recommended pipe specifications
Pipe Length (m)
L ≤ 60 m
60 m < L ≤ 100 m
If the one-way pipe length is longer than 100 m, contact Huawei technical
support.
Exhausting Nitrogen
Step 1 Remove the bonnet of the low-pressure needle valve and connect the pressure
gauge leather hose to the needle valve.
Figure 4-61 Exhausting nitrogen
(1) Low-pressure needle valve (2) Discharge pipe needle
Step 2 Open the pressure gauge valve. Loud noises of air flow are generated at first and
then disappear gradually.
Step 3 After the airflow noise disappears, remove the rubber hose and install the valve
bonnet.
Step 4 Continue exhausting nitrogen from the discharge pipe needle valve and liquid pipe
needle valve by performing
----End
Issue 13 (2023-08-20)
Recommende
d Gas Pipe
Diameter
7/8 inch
7/8 inch
Copyright © Huawei Digital Power Technologies Co., Ltd.
Recomme
nded Wall
Thickness
1.2 mm
1.2 mm
valve
Step 1
to
Step
3.
4 Installation
Recommen
Recommende
ded Liquid
d Wall
Pipe
Thickness
Diameter
5/8 inch
1.0 mm
3/4 inch
1.0 mm
(3) Liquid pipe needle valve
100

Advertisement

Table of Contents
loading

Table of Contents