Sending Settings To Device; Figure 7: View Of The Configuration-> General Tab - ABB Eagle Programming Manual

27 kv single phase recloser
Hide thumbs Also See for Eagle:
Table of Contents

Advertisement

Figure 7: View of the Configuration-> General tab
The Webpage also allows to configure the device either with Hotline tag
(HLT) or without.
If the device is configured to work without Hot Line Tag, non-reclose
mode is utilized where:

4.2.2. Sending Settings to Device

Once the desired configurations are made, the button "Save" can be used to temporarily
save the settings in the Web-HMI. The user can then proceed to other sections of the
webpages for configuration. Once all changes are done, the "Send to device" button needs
to be clicked. The settings/configuration changes are then sent to the EAGLE device.
In case the user wants to discard the changes made, "Discard Changes" button can be
pressed. Caution must be exercised when discarding changes as it discards all changes
done even in previously "Saved" but not yet sent to device changes.
The "Save"," Discard changes" and 'Send to Device" buttons are seen in all setting pages
of the Web-HMI and their behavior is similar.
1. Auto reclose is disabled
2.
the protection functions trip with settings as set in the Settings
-> Protection page
3. Hot Line Tag settings are ignored.
15

Advertisement

Table of Contents
loading

Table of Contents