T,4
6
#C, Curve Number, User defined name, Function Type α, β / Point values
C,1,FAST_RI,2,3,0.1
- Every Line Ends with CR, LF
- Fixed format ASCII values must be in Capital
- Total number of curves count and number of curves must be same.
Curve parameters validation cases are defined below:
1) Equation Based Curves:
-
Number of parameters and sequence of parameters needs to be same as defined
format else it will result into discarding of file with characteristics error to user
request.
-
All the parameters pass through range check and if any parameters is out of range
then it will result into discarding of file with characteristic error to user request.
2) Point Based Curves:
-
Maximum 20 points for a table is considered
-
If points are more than 20 than it will result into error.
-
If point is less or points not defined for higher range, then last point values will be
considered for remaining points.
-
Minimum two point (current & time) value needs to be defined.