Figure 31 Switching Communication Modes Using Nrm - ABB Eagle Programming Manual

27 kv single phase recloser
Hide thumbs Also See for Eagle:
Table of Contents

Advertisement

Eagle is able to receive the Circuit Breaker Open/Close command from control center and
also NRM signals, Auto Recloser settings, Cold Load Pickup, Lockout Reset. We can also
switch from station mode to Access Point mode and vice versa using NRM, WHMI and light
guide.
By using NRM Method
We can change (either ON to OFF or OFF to ON) within interval of 8secs We have to give BI
for 1 to 3 sec for switching modes(AP to station and vice versa) . Refer below figure for
Wi-Fi Password Reset and Wi-Fi Mode Switching using NRM Method.

Figure 31 Switching communication modes using NRM

By using WHMI
Already covered in 7.2.
By Using Light Guide
Using 1 to 3 sec light pulse three times within the interval of 30secs. Refer below figure
for Wi-Fi Enable , Wi-Fi Password Reset and Wi-Fi Mode Switching using Light Guide
Method.