Incase user credential is forgotten, then both a light source as well as a tool to toggle NRM
handle is needed to reset the password to default. The following steps needs to be
followed:
1.
Enable Wi-Fi via NRM or Light guide as explained in Section 7.1
2.
Connect to the EAGLE Wi-Fi from a device
3.
Toggle the Non Reclose Mode handle either ON->OFF-> ON or OFF->ON->OFF,
4.
Once the NRM handle sequence is complete, within 60Sec, use the light source and
point towards the light guide opening of the device
5.
Switch on the light source for 5 to 8 sec and then switch off.
6.
Within 10s turn on the light source again for another 5 to 8 seconds
7.
Once this pattern is detected the device is ready to allow admin access
8.
Connect to device Wi-Fi and open the Web HMI to enter as "Admin".
9.
Navigate to User & Access & navigate to change password and select user and change
the user password

7.3 Security

7.3.1

General Security deployment guidelines

General Security:
Technological advancements and breakthroughs have caused a significant evolution in the
electric power grid. As a result, the emerging "smart grid" and "Internet of Things" are
quickly becoming a reality. To provide end users with comprehensive real-time
information, enabling higher reliability and greater control, automation systems have
become ever more interconnected. To combat the increased risks associated with these
interconnections, ABB offers a wide range of cyber security products and solutions for
automation systems and critical infrastructure.
ABB understands the importance of cyber security and its role in advancing the security of
distribution networks. A customer investing in new ABB technologies can rely on system
solutions where reliability and security have the highest priority. At ABB, we are addressing
cyber security requirements on a system level as well as on a product level to support cyber
security standards or recommendations.
Reporting of vulnerability or cyber security issues related to any ABB product can be done
via cybersecurity@ch.abb.com.
System hardening rules
Today's distribution automation systems are basically specialized IT systems. Therefore,
several rules of hardening an automation system apply to these systems, too. EAGLE Single
phase recloser is designed from a grid automation system perspective on the lowest level
and closest to the actual primary system. It is important to apply defense-in-depth
information assurance concept where each layer in the system (which not only includes
EAGLE Singe phase recloser but other devices which might interact with it) is capable of
protecting the automation system and therefore the EAGLE Single phase recloser is also
part of this concept. The following should be taken into consideration when planning the
system protection.